05/11/2022 | PGE ELECTRIC TAG | RICHARD PRATT | PASS | MAIN PANEL UPGRADE AFTER 12PM | 5/9/2022 9:30:06 AM
5/9/2022 9:30 AM UNITED SUN ENERGY INC
GREEN CARD FOR MAIN PANEL UPGRADE AFTER 12PM
Contact Name: UNITED SUN ENERGY INC
Site Address: 9491 FREELAND DR
Phone: 5303450400
e-Mail: t.mccoy@Unitedsunenergy.com
5/11/2022 5:21:41 AM
rpratt changed Inspection Type from ELECTRICAL FINAL to PGE ELECTRIC TAG
5/11/2022 5:38:14 PM
New MSP and meter release - Approved
|
|
05/18/2022 | **PERMIT FINAL | SCOTT YOUNG | FAIL | Solar roof install final, AM inspection | 5/17/2022 8:22:54 AM
5/17/2022 8:22 AM UNITED SUN ENERGY INC
AM INSPECTION TIME
Contact Name: UNITED SUN ENERGY INC
Site Address: 9491 FREELAND DR
Phone: 5303450400
e-Mail: t.mccoy@Unitedsunenergy.com
5/19/2022 6:05:10 AM
Exceeds the 120% solar rule .
Solar breakers coming in with 90 amps
Bus bar rating of 225 amps.
Main needs to be derated to 150 amps
|
|
05/26/2022 | **PERMIT FINAL | CHRISTOPHER ROBERTS | PASS | AM INSPECTION | 5/25/2022 8:51:00 AM
5/25/2022 8:51 AM UNITED SUN ENERGY INC
AM INSPECTION, SOLAR INSTALL FINAL
Contact Name: UNITED SUN ENERGY INC
Site Address: 9491 FREELAND DR
Phone: 5303450400
e-Mail: t.mccoy@Unitedsunenergy.com
|
|