| ENV HEALTH RELEASE | BC Land Use | PASS | | |
|
| POST ELEVATION CERT | PHILO HUNT | | | |
|
07/22/2021 | PRE-GUNITE | SCOTT YOUNG | PASS | eTRAKiT Inspection Request | 7/21/2021 1:25:20 PM
7/21/2021 1:25 PM BLUE FINN INC
Contact Name: BLUE FINN INC
Site Address: 38 CHARLOTTE CT
Phone: 5308998445
e-Mail: daniewofford@sbcglobal.net
7/22/2021 2:39:47 PM
Need under construction certificate
7/22/2021 6:03:12 PM
Need under construction certificate for pool equipment house prior to pour.
7/23/2021 6:09:43 AM
Need under construction certificate for pool equipment house prior to pour.
7/23/2021 6:12:08 AM
Need under construction certificate for pool equipment house prior to pour.
|
|
12/08/2021 | PRE-DECK | ADAM KINGSLEY | PASS | P.M. is preferred | 12/7/2021 9:08:12 AM
12/7/2021 9:08 AM BLUE FINN INC
Contact Name: BLUE FINN INC
Site Address: 38 CHARLOTTE CT
Phone: 5308998445
e-Mail: daniewofford@sbcglobal.net
|
|
05/19/2022 | PRE-PLASTER | SCOTT YOUNG | PASS | eTRAKiT Inspection Request | 5/16/2022 10:04:09 AM
5/16/2022 10:04 AM BLUE FINN INC
Contact Name: BLUE FINN INC
Site Address: 38 CHARLOTTE CT
Phone: 5308998445
e-Mail: daniewofford@sbcglobal.net
5/19/2022 6:04:02 AM
Pool plumbing was inspected and passed at pre gunite
Fence up but not completed, gates not installed.
5/19/2022 6:08:49 AM
Pool plumbing was done at pre gunite.
|
|
10/04/2022 | NPDES | PWROADS | PASS | | |
|
11/03/2022 | **PERMIT FINAL | WOODY TOWNSEND | FAIL | 063289-01 MSG! -Msg! Scheduled by IVR. | 11/3/2022 12:28:14 PM
wtownsend changed Inspection Type from BACKFLOW PREVENTION to **PERMIT FINAL
11/3/2022 4:32:17 PM
1. Provide finished construction elevation certificate.
2. 200 amp sub panel underground feeders require a grounding conductor (4th wire) and all grounding and grounded (neutral) conductors shall be isolated in panel. Use anti oxidant at aluminum conductor connections. Label pool sub panel breaker in this panel and locate breaker that serves this panel.
3. Secure pool sub panel similar to 200 amp panel.
4. Install WR weather resistant receptacle at exterior of pool sub panel. Replace non WR.
5. Provide anti entrapment form issued with permit signed by owner and contractor.
6. Install lock on double gate that doesn't self close and latch.
11/30/2022 10:32:12 AM
FINAL EC ATTACHED TO PERMIT
|
|
01/26/2023 | **PERMIT FINAL | WOODY TOWNSEND | FAIL | AM request | 1/26/2023 3:40:51 PM
Complete corrections 1,2&5 From 11/3/22.
|
|