| NPDES | PWROADS | | | |
|
03/29/2021 | ENV HEALTH RELEASE | KATTY HERNANDEZ | PASS | | |
|
04/06/2021 | UNDERGROUND PLUMBING | RICHARD PRATT | CANCELLED | | 4/6/2021 7:19:27 AM
rpratt changed Inspection Date/Time from 04/06/2021 08:00 AM to 04/06/2021 08:30 AM
4/6/2021 1:58:32 PM
I added the inspection as customer only called in setbacks, he wanted. Pre-construction meeting.
|
|
04/06/2021 | FOUNDATION/FOOTINGS | RICHARD PRATT | CANCELLED | | 4/6/2021 7:19:31 AM
rpratt changed Inspection Date/Time from 04/06/2021 08:00 AM to 04/06/2021 08:30 AM
4/6/2021 1:58:36 PM
I added the inspection as customer only called in setbacks, he wanted. Pre-construction meeting.
|
|
04/06/2021 | SETBACKS | RICHARD PRATT | CANCELLED | 051105-01 - Scheduled by IVR. | 4/6/2021 7:19:35 AM
rpratt changed Inspection Date/Time from 04/06/2021 08:00 AM to 04/06/2021 08:30 AM
4/6/2021 1:58:42 PM
Needed a pre construction meeting.
|
|
04/13/2021 | UFER GROUND | RICHARD PRATT | PASS | eTRAKiT Inspection Request | 4/9/2021 3:04:17 PM
4/9/2021 3:04 PM Travis Taketa
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
4/13/2021 6:45:33 AM
rpratt changed Inspection Date/Time from 04/13/2021 08:00 AM to 04/13/2021 11:30 AM
4/13/2021 4:39:52 PM
Ufer ground installed - Approved
|
|
04/13/2021 | SETBACKS | RICHARD PRATT | PASS | eTRAKiT Inspection Request | 4/9/2021 3:04:17 PM
4/9/2021 3:04 PM Travis Taketa
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
4/13/2021 6:45:37 AM
rpratt changed Inspection Date/Time from 04/13/2021 08:00 AM to 04/13/2021 11:30 AM
4/13/2021 4:39:58 PM
Setbacks checked and approved
|
|
04/13/2021 | PIER/COLUMN FOOTINGS | RICHARD PRATT | PASS | eTRAKiT Inspection Request | 4/9/2021 3:04:17 PM
4/9/2021 3:04 PM Travis Taketa
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
4/13/2021 6:45:40 AM
rpratt changed Inspection Date/Time from 04/13/2021 08:00 AM to 04/13/2021 11:30 AM
4/13/2021 4:40:02 PM
Pier footings- Approved
|
|
04/13/2021 | FOUNDATION/FOOTINGS | RICHARD PRATT | FAIL | eTRAKiT Inspection Request | 4/9/2021 3:04:17 PM
4/9/2021 3:04 PM Travis Taketa
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
4/13/2021 6:45:44 AM
rpratt changed Inspection Date/Time from 04/13/2021 08:00 AM to 04/13/2021 11:30 AM
4/13/2021 4:40:06 PM
1) Complete form work at stem walls - check throughout.
2) Raise forms at back of garage/ house front.
3) Raise rebar in north corner of back garage.
4) Provide 1.5" clearance to forms - garage man door threshold.
5) Provide vertical reinforcement at back of garage stem wall.
6) Recall inspection when completed.
|
|
04/19/2021 | FOUNDATION/FOOTINGS | ADAM KINGSLEY | PASS | eTRAKiT Inspection Request | 4/15/2021 2:19:59 PM
4/15/2021 2:19 PM Travis Taketa
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
4/19/2021 12:49:54 PM
Previous corrections are completed.
|
|
| MASONRY GROUT | DSINSPECTION | | AM inspection request | 4/20/2021 12:59:02 PM
4/20/2021 12:59 PM Travis Taketa
Contact Name: steven Taketa
Site Address: 13901 CARVER DR
Phone: 9167103141
e-Mail: ttaketa916@yahoo.com
|
|
04/26/2021 | PRE-SLAB | ADAM KINGSLEY | PASS | eTRAKiT Inspection Request | 4/23/2021 9:06:45 AM
4/23/2021 9:06 AM Travis Taketa
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
4/26/2021 1:48:41 PM
Garage and patio
|
|
05/04/2021 | SHEAR TRANSFER | RICHARD PRATT | CANCELLED | eTRAKiT Inspection Request | 5/2/2021 7:41:26 PM
5/2/2021 7:41 PM Travis Taketa
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
5/4/2021 6:53:17 AM
rpratt changed Inspection Date/Time from 05/04/2021 08:00 AM to 05/04/2021 3:30 PM
|
|
05/04/2021 | UNDERFLOOR FRAMING | RICHARD PRATT | CANCELLED | eTRAKiT Inspection Request | 4/26/2021 6:24:43 PM
4/26/2021 6:24 PM Travis Taketa
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
5/2/2021 7:42:38 PM
5/2/2021 7:42 PM Travis Taketa
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
5/4/2021 6:53:24 AM
rpratt changed Inspection Date/Time from 05/04/2021 08:00 AM to 05/04/2021 3:30 PM
|
|
05/05/2021 | SHEAR TRANSFER | RICHARD PRATT | CANCELLED | | |
|
05/05/2021 | UNDERFLOOR FRAMING | RICHARD PRATT | CANCELLED | | |
|
05/07/2021 | UNDERFLOOR FRAMING | SCOTT YOUNG | CANCELLED | | |
|
05/07/2021 | SHEAR TRANSFER | SCOTT YOUNG | CANCELLED | | |
|
05/10/2021 | UNDERFLOOR PLUMBING | RICHARD PRATT | PASS | eTRAKiT Inspection Request | 5/6/2021 11:48:16 AM
5/6/2021 11:48 AM Travis Taketa
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
5/10/2021 12:14:13 PM
Underfloor plumbing- on test and approved
|
|
05/10/2021 | UNDERFLOOR FRAMING | RICHARD PRATT | PARTIAL | eTRAKiT Inspection Request | 5/6/2021 11:48:16 AM
5/6/2021 11:48 AM Travis Taketa
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
5/10/2021 12:14:21 PM
Provide anchor bolts within 12" of and no closer than 3.5" of each plate break- 2 on North and 1 on south elevation.
Will recheck at Shearwall inspection- Ok to sheet and insulate underfloor.
|
|
05/10/2021 | SHEAR TRANSFER | RICHARD PRATT | CANCELLED | eTRAKiT Inspection Request | 5/6/2021 11:48:16 AM
5/6/2021 11:48 AM Travis Taketa
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
5/10/2021 12:14:29 PM
Not ready.
|
|
05/10/2021 | GAS TEST | RICHARD PRATT | CANCELLED | eTRAKiT Inspection Request | 5/6/2021 11:48:17 AM
5/6/2021 11:48 AM Travis Taketa
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
5/10/2021 12:14:38 PM
Not ready
|
|
05/10/2021 | GAS PIPING | RICHARD PRATT | CANCELLED | eTRAKiT Inspection Request | 5/6/2021 11:48:17 AM
5/6/2021 11:48 AM Travis Taketa
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
5/10/2021 12:14:47 PM
Not ready
|
|
06/03/2021 | ROOF NAIL | SCOTT YOUNG | PASS | AM request | 6/2/2021 8:17:59 AM
6/2/2021 8:17 AM Travis Taketa
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
|
|
06/03/2021 | TEMP POWER | SCOTT YOUNG | PASS | AM request | 6/2/2021 8:07:47 AM
6/2/2021 8:07 AM Travis Taketa
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
|
|
06/03/2021 | SHEARWALL/B.W.P.-INT | SCOTT YOUNG | PASS | AM request | 6/2/2021 8:07:46 AM
6/2/2021 8:07 AM Travis Taketa
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
|
|
06/03/2021 | SHEARWALL/B.W.P.-EXT | SCOTT YOUNG | PASS | AM request | 6/2/2021 8:07:46 AM
6/2/2021 8:07 AM Travis Taketa
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
|
|
06/03/2021 | SHEAR TRANSFER | SCOTT YOUNG | PASS | AM Request | 4/26/2021 6:24:43 PM
4/26/2021 6:24 PM Travis Taketa
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
6/2/2021 7:12:16 AM
6/2/2021 7:12 AM Travis Taketa
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
|
|
06/17/2021 | UNDERGROUND WATER PI | SCOTT YOUNG | PASS | Am request | 6/16/2021 11:42:44 AM
6/16/2021 11:42 AM Travis Taketa
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
6/17/2021 1:23:23 PM
Cover with sand prior to back filling with native soil. Take pictures before covering.
6/17/2021 1:40:12 PM
Cover with sand prior to back filling with native soil. Take pictures before covering.
6/17/2021 11:37:12 PM
Sand conduit prior to backfilling with native soil.
Take pictures to verify prior to filling in trench
|
|
| FOUNDATION/FOOTINGS | DSINSPECTION | | eTRAKiT Inspection Request | 6/18/2021 8:04:00 AM
6/18/2021 8:03 AM Travis Taketa
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
|
|
| PIER/COLUMN FOOTINGS | DSINSPECTION | | eTRAKiT Inspection Request | 6/18/2021 8:04:00 AM
6/18/2021 8:03 AM Travis Taketa
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
|
|
| SETBACKS | DSINSPECTION | | eTRAKiT Inspection Request | 6/18/2021 8:04:00 AM
6/18/2021 8:03 AM Travis Taketa
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
|
|
| UFER GROUND | DSINSPECTION | | eTRAKiT Inspection Request | 6/18/2021 8:04:00 AM
6/18/2021 8:03 AM Travis Taketa
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
|
|
07/02/2021 | 4-WAY ROUGH FRAME | ADAM KINGSLEY | FAIL | eTRAKiT Inspection Request | 6/30/2021 11:40:56 AM
6/30/2021 11:40 AM Travis Taketa
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
7/2/2021 12:04:43 PM
1. Building not dried in. Provide water barrier/house wrap or equal. Install missing window in master bedroom or equal.
2. Electrical rough in not ready. Complete branch circuit home runs, make up grounds in device boxes, nail plates as needed.
3. Cover HVAC supply and return air registers or equal protection from construction debris.
4. Supply air flexible ducts overbent/pinching at master bedroom supply and incomplete at hallway.
5. Annular space around tub drain open, exposed underfloor. Provide 1/4" wire mesh , blocking or equal rat proofing.
Recall inspection after corrections completed
|
|
07/06/2021 | 4-WAY ROUGH FRAME | RICHARD PRATT | CANCELLED | Pm request | 7/2/2021 12:05:45 PM
7/2/2021 12:05 PM Travis Taketa
Pm request
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
7/6/2021 7:05:05 AM
rpratt changed Inspection Date/Time from 07/06/2021 12:00 PM to 07/06/2021 1:00 PM
7/6/2021 7:14:18 AM
rpratt changed Inspection Date/Time from 07/06/2021 01:00 PM to 07/06/2021 2:00 PM
7/6/2021 8:34:08 AM
Contractor texted and canceled - still working on correction list
|
|
07/07/2021 | 4-WAY ROUGH FRAME | SCOTT YOUNG | CANCELLED | PM REQUEST | 7/7/2021 1:51:47 PM
Cancelled by contractor, not ready.
|
|
07/08/2021 | 4-WAY ROUGH FRAME | SCOTT YOUNG | PARTIAL | eTRAKiT Inspection Request | 7/7/2021 1:29:00 PM
7/7/2021 1:28 PM Travis Taketa
PM Please
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
7/9/2021 6:19:12 AM
All corrections have been completed, except for the main panel being wired.
Ok to insulate.
|
|
08/24/2021 | GAS TEST | ADAM KINGSLEY | FAIL | Will not be able to be on site for insp. | 8/23/2021 11:03:38 AM
8/23/2021 11:03 AM Travis Taketa
Please call steve 916-710-3141
or travis 916-501-4211 if you need anything.
There is lock box CODE 0425 on the water spicket with the key needed to get into the house.
A ladder will be in the house for use if needed.
The gauge for the gas line is in the garage north wall.
Plans are availible inside of the house with sign off sheet on table.
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
8/24/2021 3:47:59 PM
1. System not holding pressure and less than minimum psi test. Gauge at 6psi, dropping. Provide minimum 10psi for 15 minutes or equal.
|
|
08/30/2021 | GAS TEST | WOODY TOWNSEND | PASS | eTRAKiT Inspection Request | 8/27/2021 11:46:03 AM
8/27/2021 11:46 AM Travis Taketa
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
8/30/2021 5:19:51 PM
House test
|
|
11/08/2021 | UNDERGROUND GAS | RICHARD PRATT | PASS | eTRAKiT Inspection Request | 11/5/2021 1:00:34 PM
11/5/2021 1:00 PM Travis Taketa
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
11/8/2021 6:56:49 AM
rpratt changed Inspection Date/Time from 11/08/2021 08:00 AM to 11/08/2021 1:30 PM
11/8/2021 1:06:25 PM
LP Gas trench, conduit and psi test - Approved
|
|
11/08/2021 | TAG LPG | RICHARD PRATT | PASS | eTRAKiT Inspection Request | 11/5/2021 1:00:34 PM
11/5/2021 1:00 PM Travis Taketa
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
11/8/2021 6:56:56 AM
rpratt changed Inspection Date/Time from 11/08/2021 08:00 AM to 11/08/2021 1:30 PM
11/8/2021 1:06:33 PM
LP Gas tag - Approved
|
|
11/30/2021 | **PERMIT FINAL | SCOTT YOUNG | FAIL | eTRAKiT Inspection Request | 11/25/2021 1:25:50 PM
11/25/2021 1:25 PM Travis Taketa
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
11/28/2021 10:03:07 AM
11/28/2021 10:03 AM Travis Taketa
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
11/30/2021 6:40:18 PM
Not ready, walked around house pointing out issues they will need to deal with.
|
|
02/17/2022 | **PERMIT FINAL | RICHARD PRATT | FAIL | eTRAKiT Inspection Request | 2/11/2022 8:26:17 AM
2/11/2022 8:26 AM Travis Taketa
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
2/17/2022 6:19:37 AM
rpratt changed Inspection Date/Time from 02/17/2022 08:00 AM to 02/17/2022 3:30 PM
2/17/2022 5:06:36 PM
1. Complete HERS Documentation with CalCerts.
2. Adjust front and rear elevation stair tread height to be with in 3/8" of each other.
3. Adjust balusters to be no more than 4" apart.
4. Provide a removable screw type cap for DWV clean out rear and south elevation.
5. Secure condenser to the pad.
6. Label breakers in manual disconnect.
7. Repair stove exhaust fan duct - will not hold a single sheet of paper.
8. Seal around drier duct in Laundry.
9. Provide a cover plate for FAU receptacle in attic.
10. Clean debris from FAU pan in attic.
11. Recall inspection when completed.
Repair Fire Sprinkler alarm bell - did not sound off during test.
Recall inspection when completed
|
|
03/03/2022 | CAL FIRE FINAL INSPE | CHRIS BOYD | PASS | | 3/3/2022 11:19:04 AM
Applicant has made corrections around the LPG tank. has met all fire criteria.
|
|
03/30/2022 | **PERMIT FINAL | RICHARD PRATT | PASS | eTRAKiT Inspection Request | 3/28/2022 6:41:59 AM
3/28/2022 6:41 AM Travis Taketa
Contact Name: Travis Taketa
Site Address: 13901 CARVER DR
Phone: 9165014211
e-Mail: ttaketa916@yahoo.com
3/30/2022 5:32:28 PM
Complete the HERS Documentation with CalCerts.
Recall inspection when completed.
4/5/2022 6:15:06 AM
Final correction items completed
|
|