Permit No. B20-0973 Permit Type   ACCESSORY DWELLING UNIT Site Address   93 KENDAL CT
CHICO, CA 95973
Applied   04/13/2020 Applicant   LARRY
Approved   05/27/2020 Owner   RUBY FAMILY TRUST
Issued   06/01/2020 Contractor   OWNER BUILDER
Parent Permit No.   Description   ADU (2035) GAR (1324) COVD (753)
  Notes  
 
  Date of Inspection Inspection Type Inspector Result Remarks Notes

 07/08/2020FOUNDATION/FOOTINGSSCOTT YOUNGPASS043532-01 MSG! -Msg! Scheduled by IVR.

 07/14/2020PRE-SLABADAM KINGSLEYPASS043735-01 - Scheduled by IVR.

 07/23/2020UNDERFLOOR FRAMINGWOODY TOWNSENDPASS044052-01 - Scheduled by IVR.

 07/23/2020UNDERFLOOR PLUMBINGWOODY TOWNSENDPASS

 08/25/2020SHEARWALL/B.W.P.-EXTWOODY TOWNSENDPASS045055-01 MSG! -Msg! Scheduled by IVR.

 08/25/2020ROOF NAILWOODY TOWNSENDPASS8/25/2020 2:07:40 PM Eve roof sheathing is not fire resistant. Fire resistive eves will be required prior to final.

 11/13/2020PGE ELECTRIC TAGSCOTT YOUNGCANCELLEDNOT READY11/12/2020 12:21:48 PM PM PLEASE

 12/01/2020PGE ELECTRIC TAGWOODY TOWNSENDPASS

 12/01/2020UNDERGROUND ELECTRICWOODY TOWNSENDPASS047860-01 MSG! -Msg! Scheduled by IVR.12/1/2020 3:31:28 PM wtownsend changed Inspection Type from TAG ELECTRIC to UNDERGROUND ELECTRIC

 01/25/20214-WAY ROUGH FRAMEWOODY TOWNSENDFAILeTRAKiT Inspection Request1/21/2021 9:12:47 AM 1/21/2021 9:12 AM Larry Ruby Afternoon inspection is best but not essential. Contact Name: Larry Ruby Site Address: 93 KENDAL CT Phone: 5306248361 e-Mail: larry@sheratonrem.com 1/25/2021 3:27:57 PM 1. Test abs DWV. 2. Secure DWV at mid span. 3. Install ducts for bath fans. 4. Run individual conductors in conduit at sub panels. 5. Repair or replace over bored studs at sub panel area. 6. Dedicate 20 amp circuit for laundry room. 7. Wire receptacle at over 2' wall in bedroom. 8. Complete water supply plumbing at shower and well pressure tank and test supply pipe. 9. Provide approved truss calcs. 10. Provide approved energy calcs. 11 vent kitchen sink per code. 12. Terminate primary condensate line to exterior. QII insulation required.

 02/09/20214-WAY ROUGH FRAMEWOODY TOWNSENDFAILMorning is best if it works.2/8/2021 8:32:30 AM 2/8/2021 8:32 AM Larry Ruby Contact Name: Larry Ruby Site Address: 93 KENDAL CT Phone: 5306248361 e-Mail: larry@sheratonrem.com 2/9/2021 3:14:57 PM 1. Provide test on fire sprinklers. 2. Bond gas pipe. 3. Isolate grounding and grounded conductors at sub panel and bond panels. Okay to insulate walls.

 02/09/2021UNDERGROUND PLUMBINGWOODY TOWNSENDPASS2/9/2021 3:15:46 PM Water pipe and conduit from well to house.

 02/11/20214-WAY ROUGH FRAMEWOODY TOWNSENDPASS

 04/06/2021GAS PIPINGSCOTT YOUNGPASS051104-01 MSG! -Msg! Scheduled by IVR.

 04/09/2021UNDERGROUND GASADAM KINGSLEYPASS051293-01 - Scheduled by IVR.4/9/2021 8:06:56 AM PE pipe tank to dwelling, and test -approved. LPG tag issued 325g tank.

 12/21/2021ENV HEALTH RELEASEPAUL THAOPASS5/27/2020 8:28:26 AM Pending septic final for release. 12/21/2021 9:01:03 AM Well and septic finaled. Pass

 12/21/2021CAL FIRE FINAL INSPECHRIS BOYDPASS

 12/22/2021**PERMIT FINALSCOTT YOUNGFAILAM REQUEST12/22/2021 10:50:09 AM 1. Grab bars required at all stair rails. 2. Back deck is at 35" code requires a hand rail over 30" 3. Grading has not been completed around house, areas are pooling and cause for concern. 4. Min. Code requirements are 5% ( 10' out = 6" drop ) 5. Have HERS testing completed. 6. Washing machine receptacle must be GFCI, either GFCI receptacle or GFCI BREAKER in the panel. 7. Finish railing in garage 8. All garage receptacles must be GFCI . 9 . Anti syphon / back flow devices required on all exterior hose bibs. 10. Remove all paper/ plastic covering exterior vents. 11. Finish and install underfloor access door. 12. Insulated water lines to water heater lines. 13. Insulate water main entering house. 14. Drip leg / sediment trap required on gas lines at attic furnace and water heater. 12/23/2021 6:09:35 AM 1. Grab bars required at all stair rails. 2. Back deck is at 35" code requires a hand rail over 30" 3. Grading has not been completed around house, areas are pooling and cause for concern. 4. Min. Code requirements are 5% ( 10' out = 6" drop ) 5. Have HERS testing completed. 6. Washing machine receptacle must be GFCI, either GFCI receptacle or GFCI BREAKER in the panel. 7. Finish railing in garage 8. All garage receptacles must be GFCI . 9 . Anti syphon / back flow devices required on all exterior hose bibs. 10. Remove all paper/ plastic covering exterior vents. 11. Finish and install underfloor access door. 12. Insulated water lines to water heater lines. 13. Insulate water main entering house. 14. Drip leg / sediment trap required on gas lines at attic furnace and water heater.

 02/04/2022**PERMIT FINALSCOTT YOUNGPASS2/3/2022 3:50:24 PM PM PLEASE 2/4/2022 4:42:11 PM All corrections have been completed 2/7/2022 6:10:06 AM All corrections have been completed