02/20/2020 | GAS TEST | ADAM KINGSLEY | PASS | 039244-01 - Scheduled by IVR. | 2/20/2020 2:08:34 PM
Underground gas & electric conduit included. LPG tag issued for 288g tank
|
|
03/09/2020 | **PERMIT FINAL | WOODY TOWNSEND | FAIL | 039811-01 - Scheduled by IVR. | 3/9/2020 3:11:49 PM
1. Install conductors run through existing telephone box in conduit or use electrical box listed for use.
2. Provide final flood cert.
All that's needed for final.
|
|
03/17/2020 | **PERMIT FINAL | WOODY TOWNSEND | CANCELLED | | |
|
04/09/2020 | **PERMIT FINAL | WOODY TOWNSEND | CANCELLED | eTRAKiT Inspection Request | 4/7/2020 8:13:31 AM
4/7/2020 8:13 AM LONNIE R UNRUH
Contact Name: Michael Robinson
Site Address: 4125 NIGHTHAWK WAY
Phone: 5305203337
e-Mail: MICHAEL@GENERACSMARTGEN.COM
4/9/2020 1:23:19 PM
CONTRACTOR CALLED 10 MINUTES PRIOR TO INSPECTION TO CANCEL. HOMEOWNER LOCKED GATE AND COULD NOT BE FOUND TO PROVIDE ACCESS
|
|
04/13/2020 | **PERMIT FINAL | WOODY TOWNSEND | FAIL | eTRAKiT Inspection Request | 4/9/2020 4:02:09 PM
4/9/2020 4:02 PM LONNIE R UNRUH
Contact Name: Michael Robinson
Site Address: 4125 NIGHTHAWK WAY
Phone: 5305203337
e-Mail: MICHAEL@GENERACSMARTGEN.COM
4/13/2020 12:15:44 PM
Conductors still exposed inside phone box. Conduit shall be used from main to gutter.
Final flood cert received and approved.
5/11/2020 9:30:52 AM
Corrections complete.Permit finaled.
|
|
04/13/2020 | POST ELEVATION CERT | WOODY TOWNSEND | PASS | | |
|