01/23/2020 | ENV HEALTH RELEASE | VANCE SEVERIN | PASS | | |
|
04/13/2020 | FOUNDATION/FOOTINGS | SCOTT YOUNG | PASS | 040824-01 - Scheduled by IVR. | 4/13/2020 7:00:55 AM
syoung changed Inspection Date/Time from 04/13/2020 08:00 AM to 04/13/2020 12:00 PM
4/13/2020 4:44:20 PM
Also inspected set backs
Eupher ground
Pier and column footing
|
|
07/14/2020 | PRE-SLAB | RICHARD PRATT | PASS | garage slab rebar | 7/14/2020 6:43:28 AM
rpratt changed Inspection Date/Time from 07/14/2020 08:00 AM to 07/14/2020 1:30 PM
7/14/2020 6:54:17 AM
rpratt changed Inspection Date/Time from 07/14/2020 01:30 PM to 07/14/2020 2:00 PM
7/14/2020 8:13:34 PM
Pre slab approved
|
|
07/14/2020 | UNDERFLOOR PLUMBING | RICHARD PRATT | PASS | | 7/14/2020 6:43:34 AM
rpratt changed Inspection Date/Time from 07/14/2020 08:00 AM to 07/14/2020 1:00 PM
7/14/2020 6:54:24 AM
rpratt changed Inspection Date/Time from 07/14/2020 01:00 PM to 07/14/2020 2:00 PM
7/14/2020 8:13:41 PM
Underfloor plumbing approved
|
|
07/14/2020 | UNDERFLOOR FRAMING | RICHARD PRATT | PASS | | 7/14/2020 6:43:41 AM
rpratt changed Inspection Date/Time from 07/14/2020 08:00 AM to 07/14/2020 1:30 PM
7/14/2020 6:54:30 AM
rpratt changed Inspection Date/Time from 07/14/2020 01:30 PM to 07/14/2020 2:00 PM
7/14/2020 8:13:48 PM
Underfloor framing-approved
|
|
07/14/2020 | UNDERGROUND PLUMBING | RICHARD PRATT | PASS | | 7/14/2020 8:14:29 PM
Underground plumbing and trench inspection approved
|
|
10/05/2020 | SHEARWALL/B.W.P.-EXT | RICHARD PRATT | PARTIAL | | 10/5/2020 7:29:13 AM
rpratt changed Inspection Date/Time from 10/05/2020 08:00 AM to 10/05/2020 4:30 PM
10/5/2020 7:10:41 PM
Provide a letter from the engineer not requiring cs14 strapping at door and window openings per 16/S6 & 17/S6.
Provide letter prior to covering exterior.
|
|
10/05/2020 | ROOF FRAME/SHEATHING | RICHARD PRATT | CANCELLED | 046155-01 - Scheduled by IVR. | 10/5/2020 7:29:20 AM
rpratt changed Inspection Date/Time from 10/05/2020 08:00 AM to 10/05/2020 4:30 PM
10/5/2020 7:10:47 PM
Not ready for roof nail Orr truss inspection
|
|
10/28/2020 | ROOF NAIL | SCOTT YOUNG | PASS | AM REQUESTED | 10/28/2020 11:57:09 AM
A-35 's required at all bottom cord to top plate connections at gable ends.
|
|
02/05/2021 | PGE ELECTRIC TAG | SCOTT YOUNG | FAIL | | 2/4/2021 11:24:40 AM
PM PLEASE - WILL BE AVAILABLE AT THE JOB SITE THEN
2/5/2021 12:17:53 PM
Panel has not been wired,
Need to have a min.20 amp circuit to a GFCI outlet with waterproof cover.
|
|
02/05/2021 | ROUGH PLUMBING | SCOTT YOUNG | PASS | | 2/4/2021 11:24:29 AM
PM PLEASE - WILL BE AVAILABLE AT THE JOB SITE THEN
2/5/2021 12:18:02 PM
syoung changed Inspection Type from FIRE SPRINKLERS to ROUGH PLUMBING
|
|
02/10/2021 | 4-WAY ROUGH FRAME | SCOTT YOUNG | PASS | | 2/10/2021 6:44:27 PM
Secure gas flex line in laundry rm.
Ground all metal boxes with listed green ground screw.
Rodent proof drains to tubs through floor. Wire mesh or like.
Furnace not installed.
Ok to insulate.
|
|
03/15/2021 | PGE GAS TAG | ADAM KINGSLEY | FAIL | | 3/15/2021 3:44:05 PM
1. Test gauge reads 0psi. Provide minimum 10psi for 15 minutes. Recall inspection after corrections addressed.
|
|
03/24/2021 | PGE GAS TAG | RICHARD PRATT | PASS | | 3/24/2021 6:40:41 AM
rpratt changed Inspection Date/Time from 03/24/2021 08:00 AM to 03/24/2021 09:30 AM
|
|
02/28/1850 | NPDES | PWROADS | | VOIDED (ALK 6/17/2021) | 6/17/2021 7:52:40 PM
Inspection voided by ALK.
|
|
06/18/2021 | **PERMIT FINAL | ADAM KINGSLEY | FAIL | | 6/17/2021 8:34:58 AM
PREFER RICHARD
6/18/2021 2:30:20 PM
1. Provide arc-fault protection for 15A & 20A interior living space circuits, except bathrooms
2. Provide a Pressure reducer at water service to building, pressure is excess of 80psi.
3. Missing handrail at deck, provide graspable handrail between 34"-38" above stair nosing.
4. Missing kitchen island receptacle
5. Kitchen hood not operational
6. Living room receptacle test open ground
7. Provide single luminaire controlled by vacancy sensor or equal at bathrooms, laundry and garage
8. Garage pedestrian door missing solid landing. Provide minimum 3' x door width landing.
9. Provide CalFire final clearance
10. Connect fire sprinkler flow switch to alarm bell or equal.
|
|
07/08/2021 | **PERMIT FINAL | SCOTT YOUNG | PARTIAL | 053194-01 - Scheduled by IVR. | 7/9/2021 6:18:34 AM
All previous corrections have been completed, except for garage door.
Call fire still needs to be signed off .
|
|
07/21/2021 | CAL FIRE FINAL INSPE | CHRIS BOYD | PASS | | |
|
07/07/2022 | **PERMIT FINAL | RANDALL SMITH | PASS | 060776-01 MSG! -Msg! Scheduled by IVR. | 7/5/2022 3:34:46 PM
PM PLEASE
7/7/2022 2:40:58 PM
Passed
|
|