07/09/2020 | UNDERGROUND ELECTRIC | SCOTT YOUNG | FAIL | 043597-01 - Scheduled by IVR. | 7/9/2020 11:58:44 AM
Trench has been back filled, unable to verify depth.
Main panel is located on a pump house, you are required by code to have one working receptacle on a 20 amp circuit in a listed waterproof box. Ground rods are not placed at a min. Of 6' apart and will need to be corrrected.
Make appropriate corrections and
Call for reinspection
|
|
07/14/2020 | UNDERGROUND ELECTRIC | RICHARD PRATT | CANCELLED | 043748-01 - Scheduled by IVR. | 7/14/2020 6:43:22 AM
rpratt changed Inspection Date/Time from 07/14/2020 08:00 AM to 07/14/2020 4:00 PM
7/14/2020 6:54:11 AM
rpratt changed Inspection Date/Time from 07/14/2020 04:00 PM to 07/14/2020 4:30 PM
7/14/2020 8:13:28 PM
Not underground electrical temp power meter release is what should've been called.
|
|
07/14/2020 | TEMP POWER | RICHARD PRATT | PASS | | 7/14/2020 8:14:36 PM
Temp power meter release approved
|
|
08/03/2020 | FOUNDATION/FOOTINGS | ADAM KINGSLEY | FAIL W/RE-INSP FEE | 044403-01 - Scheduled by IVR. | 8/3/2020 10:12:29 AM
1. Approved plans not provided for inspection. Reinspection fee added.
|
|
08/04/2020 | FOUNDATION/FOOTINGS | SCOTT YOUNG | PASS | 044427-01 - Scheduled by IVR. | |
|
10/30/2020 | CONTINUITY TEST | WOODY TOWNSEND | PASS | 046994-06 - Scheduled by IVR. | |
|
10/30/2020 | UNDERGROUND WATER PI | WOODY TOWNSEND | PASS | 046994-04 - Scheduled by IVR. | |
|
10/30/2020 | MANOMETER TEST | WOODY TOWNSEND | PASS | 046994-05 - Scheduled by IVR. | |
|
10/30/2020 | SEWER(PIPE/TEST/TAP) | WOODY TOWNSEND | PASS | 046994-03 - Scheduled by IVR. | |
|
10/30/2020 | UNDERGROUND ELECTRIC | WOODY TOWNSEND | PASS | 046994-02 - Scheduled by IVR. | |
|
10/30/2020 | GAS TEST | WOODY TOWNSEND | FAIL | 046994-01 - Scheduled by IVR. | 10/30/2020 4:31:10 PM
Provide test on underground gas pipe. Backfill at own risk.
|
|
11/19/2020 | GAS TEST | RICHARD PRATT | PASS | 047618-01 - Scheduled by IVR. | 11/19/2020 7:37:35 AM
rpratt changed Inspection Date/Time from 11/19/2020 08:00 AM to 11/19/2020 4:00 PM
11/19/2020 7:01:36 PM
Gas psi test - approved
|
|
12/21/2020 | **PERMIT FINAL | SCOTT YOUNG | FAIL | 048398-01 - Scheduled by IVR. | 12/22/2020 6:45:53 AM
1. A/C condenser has a 25 max amp rating on the manufacture sticker, 30 amp breaker's installed.
2. Tamper resistant caps on Freon lines to condenser.
3. Anti siphon devises on all exterior hose bibs .
4. Drip leg required at hot water heater gas connection.
5. North end of home does not meet min. Grade requirement, 5% drop, equivalent to 6" drop in 10'
They will need to divert water, you can see where it is pooling, condenser sits in the middle of it.
Suggest French drain or like to divert water from driveway.
6. Cal fire sign off required.
7. Environmental health sign off required.
8. 433-A paperwork needed.
|
|
12/30/2020 | 433A | PERMIT CENTER | PASS | RCVD ALL DOCS | 12/30/2020 11:09:08 AM
RCVD MCO, GRANT DEED, AND $22 CHECK FOR HCD
10/29/2021 3:30:03 PM
NEW CHECK #5602 FOR $22 IN SAFE
|
|
12/30/2020 | CAL FIRE FINAL INSPE | JOHN GADDIE | PASS | | 12/30/2020 12:02:30 PM
OK to Final
|
|
01/08/2021 | ENV HEALTH RELEASE | KATTY HERNANDEZ | PASS | | 1/8/2021 5:02:31 PM
RECEIVED WATER LAB RESULTS.
|
|
01/19/2021 | **PERMIT FINAL | RICHARD PRATT | FAIL W/RE-INSP FEE | 049032-01 - Scheduled by IVR. | 1/19/2021 6:58:38 AM
rpratt changed Inspection Date/Time from 01/19/2021 08:00 AM to 01/19/2021 2:30 PM
1/19/2021 6:29:35 PM
Provide access to the modular to verify sediment trap is installed at the water heater.
Label the main Service Panel.
Pay Re-inspection fee, and recall inspection when completed.
|
|
11/23/2021 | MECHANICAL FINAL | SCOTT YOUNG | PASS | 055915-01 - Scheduled by IVR. | 11/23/2021 2:30:16 PM
Corrections have been completed
|
|