02/20/2020 | FOUNDATION/FOOTINGS | WOODY TOWNSEND | PASS | | 2/20/2020 4:01:53 PM
Ufer approved.
|
|
03/02/2020 | UNDER SLAB PLUMBING | PHILLIP MYERS | PASS | | |
|
03/17/2020 | PRE-SLAB | SCOTT YOUNG | CANCELLED | | |
|
04/01/2020 | PRE-SLAB | SCOTT YOUNG | PASS | | 4/1/2020 10:17:21 AM
syoung changed Inspection Date/Time from 04/01/2020 08:00 AM to 04/01/2020 12:30 PM
4/1/2020 6:11:31 PM
Also looked at the footings for front and back porches, garage pre slab was not looked at.syoung changed Inspection Date/Time from 04/01/2020 08:00 AM to 04/01/2020 12:30 PM
4/1/2020 9:00:08 PM
Also looked at the footings for front and back porches, garage pre slab was not looked at.syoung changed Inspection Date/Time from 04/01/2020 08:00 AM to 04/01/2020 12:30 PM
4/1/2020 9:41:28 PM
Also looked at the footings for front and back porches, garage pre slab was not looked at.syoung changed Inspection Date/Time from 04/01/2020 08:00 AM to 04/01/2020 12:30 PM
4/2/2020 6:01:08 AM
Also looked at the footings for front and back porches, garage pre slab was not looked at.syoung changed Inspection Date/Time from 04/01/2020 08:00 AM to 04/01/2020 12:30 PM
4/2/2020 6:12:24 AM
Also looked at the footings for front and back porches, garage pre slab was not looked at.syoung changed Inspection Date/Time from 04/01/2020 08:00 AM to 04/01/2020 12:30 PM
|
|
04/23/2020 | PRE-SLAB | ADAM KINGSLEY | PASS | PRE SLAB FOR GAR, FRONT AND BACK PORCH | 4/23/2020 5:50:06 AM
akingsley changed Inspection Date/Time from 04/23/2020 08:00 AM to 04/23/2020 09:30 AM
4/23/2020 9:37:16 AM
Remaining slabs
|
|
| PLANNING CLEARANCE | TRISTAN WEEMS | NOT REQUIRED | | 1/28/2020 8:17:15 AM
Need recorded second dwelling
5/8/2020 8:12:24 AM
See planning note.
|
|
07/08/2020 | SHEARWALL/B.W.P.-EXT | ADAM KINGSLEY | FAIL | | 7/8/2020 11:04:51 AM
1. Missing nuts at HD anchors several locations. Provide required nuts or equal.
2. Missing STC clips at truss to interior wall connections. Provide per plans or equal.
3. Provide MSTA 30 at garage/porch top plate splice per plans, or equal.
4. Complete gable end bracing per 4/SD3 & roof plan or equal. Missing ceiling blocks & brace at 5' oc.
5. Missing truss web bracing at 3 locations. Provide web bracing per truss sheets at A07A, A10, A11 or equal.
Ok to proceed and cover exterior only. All corrections are to remain exposed for inspection.
7/8/2020 11:32:30 AM
1. Missing nuts at HD anchors several locations. Provide required nuts or equal.
2. Missing STC clips at truss to interior wall connections. Provide per plans or equal.
3. Provide MSTA 30 at garage/porch top plate splice per plans, or equal.
4. Complete gable end bracing per 4/SD3 & roof plan or equal. Missing ceiling blocks & brace at 5' oc.
5. Missing truss web bracing at 3 locations. Provide web bracing per truss sheets at A07A, A10, A11 or equal.
Ok to proceed and cover exterior only. All corrections are to remain exposed for inspection.
|
|
07/08/2020 | ROOF NAIL | ADAM KINGSLEY | PASS | | |
|
08/07/2020 | 4-WAY ROUGH FRAME | WOODY TOWNSEND | PARTIAL | | 8/7/2020 11:54:42 AM
Okay to proceed with insulation/ drywall.
Comply with WUI Fire resistive soffit at eaves with approved vents by final.
|
|
08/07/2020 | PGE ELECTRIC TAG | WOODY TOWNSEND | PASS | | |
|
12/04/2020 | UNDERGROUND WATER PI | ADAM KINGSLEY | PASS | | 12/4/2020 1:57:51 PM
SFD to meter
|
|
12/04/2020 | UNDERGROUND GAS | ADAM KINGSLEY | PASS | | 12/4/2020 5:20:58 PM
Tank to SFD (street side) & whole system gas test approved. Lpg tag issued
|
|
02/28/1850 | NPDES | PWROADS | | VOIDED (RLF 12/16/2020) | 12/16/2020 8:11:24 AM
Inspection voided by RLF.
|
|
12/16/2020 | PW FINAL | PWROADS | PASS | SEE NOTES | 12/16/2020 8:11:59 AM
SEE ENCROACHMENT PERMIT PW19-0216
|
|
02/09/2021 | CAL FIRE FINAL INSPE | CHRIS BOYD | PASS | | |
|
02/24/2021 | **PERMIT FINAL | SCOTT YOUNG | FAIL | 050026-01 MSG! -Msg! Scheduled by IVR. | 2/24/2021 11:12:22 AM
1. A/C condenser has a max. Amp rating of 20 amps, disconnect has 30 amp fuses.
2. Tamper resistant caps on condenser lines at unit are required.
3.Cal certs hers report not finished.
4.environmental health sign off pending.
2/24/2021 5:44:19 PM
1. A/C condenser has a max. Amp rating of 20 amps, disconnect has 30 amp fuses.
2. Tamper resistant caps on condenser lines at unit are required.
3.Cal certs hers report not finished.
4.environmental health sign off pending.
2/24/2021 6:56:21 PM
1. A/C condenser has a max. Amp rating of 20 amps, disconnect has 30 amp fuses.
2. Tamper resistant caps on condenser lines at unit are required.
3.Cal certs hers report not finished.
4.environmental health sign off pending.
|
|
02/25/2021 | **PERMIT FINAL | SCOTT YOUNG | PASS | 050074-01 - Scheduled by IVR. | 3/1/2021 6:05:08 AM
Corrections completed.
|
|