| CAL FIRE FINAL INSPE | CHRIS BOYD | | | |
|
02/28/1850 | NPDES | PWROADS | | VOIDED (SLN 11/1/2019) | 11/1/2019 9:27:01 AM
Inspection voided by SLN.
|
|
| ENV HEALTH RELEASE | YVETTE CASTANON | PASS | | |
|
| FOUNDATION/FOOTINGS | DSINSPECTION | | VOIDED (MJP2 2/18/2020) | 2/18/2020 3:51:15 PM
Inspection voided by MJP2. Most recent remarks follow: 039235-01 - Scheduled by IVR.
|
|
02/19/2020 | FOUNDATION/FOOTINGS | WOODY TOWNSEND | FAIL | | 2/19/2020 5:05:14 PM
1. Provide stable soil at 45 degree angle from bottom of footings at Two locations in front of trees at shear slope.
|
|
02/20/2020 | FOUNDATION/FOOTINGS | SCOTT YOUNG | PASS | | 2/19/2020 5:04:08 PM
Am req before 9:30
|
|
09/18/2020 | **PERMIT FINAL | ADAM KINGSLEY | FAIL | eTRAKiT Inspection Request | 9/16/2020 12:27:32 PM
9/16/2020 12:27 PM RIDGE BUILDERS LLC
Contact Name: RIDGE BUILDERS LLC
Site Address: 4569 RIM VIEW DR
Phone: 5304139110
e-Mail: KR@RIDGEBUILDERSLTD.COM
9/18/2020 12:50:42 PM
1. Permit is for barn with no electric. Update permit to add electrical & provide approved plan(s).
2. Provide solid surface landings at exterior pedestrian doors (two locations). Min 3' deep x door width.
3. Provide safety glazing (both panes tempered) or equal for window left of front door (within 2' of door edge) .
4. Provide GFCI protection for all 15A & 20A receptacles.
5. Provide metal building bond & equipotential bonding grid bond to grounding system or equal.
6. Missing exterior lighting at pedestrian doors. Provide lighting or equal.
CalFire clearances verified by signed inspection card on site
Note: WUI compliant windows/glazing not provided. building is 50' or more from dwelling, WUI exception.
|
|
01/29/2021 | **PERMIT FINAL | ADAM KINGSLEY | PASS | eTRAKiT Inspection Request | 1/27/2021 2:19:36 PM
1/27/2021 2:19 PM RIDGE BUILDERS LLC
Contact Name: RIDGE BUILDERS LLC
Site Address: 4569 RIM VIEW DR
Phone: 5305202374
e-Mail: kr@ridgebuildersltd.com
1/29/2021 11:15:26 AM
Previous corrections are completed.
CalFire final clearance field verified.
|
|