07/14/2020 | FOUNDATION/FOOTINGS | SCOTT YOUNG | PASS | eTRAKiT Inspection Request | 7/13/2020 12:56:40 PM
7/13/2020 12:56 PM Michael Houar
Contact Name: Michael Houar
Site Address: 1215 BLOCK RD
Phone: 5308934741
e-Mail: TheRemodelors@att.net
|
|
08/10/2020 | **PERMIT FINAL | RICHARD PRATT | FAIL | | 8/10/2020 6:51:34 AM
rpratt changed Inspection Date/Time from 08/10/2020 09:00 AM to 08/10/2020 09:00 AM
8/12/2020 5:56:22 AM
Provide Placard or Directory per 705.10 CEC at each disconnecting means.
Provide boring documentation for work done from Main Residence MSP and Ag MSP. For Permit B19-3353 and B19-3355
The original Inspection items are still required to be completed.
No re-inspection fee as per CJ.
8/19/2020 6:43:12 AM
Original Inspection Items:
Provide a solid surface for the MSP (Main Service Panel) and the Sub Panel to be mounted. The plywood is rotted and neither are safely nor properly secured.
Repair conduit to the MSP from the service drop and the feeder.
Provide a Dead Front for the MSP.
Provide a clear working area in front of both panels.
Underground Electrical trench and conduit was not inspected, open up the trench for inspection near MSP & Sub Panel.
Provide a directory/ placard showing the location of each disconnecting means on the property and place one at each location.
Provide a 10' vegetation free area around the array.
Recall inspection when completed.
|
|
08/06/2020 | **PERMIT FINAL | RICHARD PRATT | FAIL | see B19-3533 for original array | 8/6/2020 8:14:16 PM
Provide a solid surface for the MSP (Main Service Panel) and the Sub Panel to be mounted. The plywood is rotted and neither are safely nor properly secured.
Repair conduit to the MSP from the service drop and the feeder.
Provide a Dead Front for the MSP.
Provide a clear working area in front of both panels.
Underground Electrical trench and conduit was not inspected, open up the trench for inspection near MSP & Sub Panel.
Provide a directory/ placard showing the location of each disconnecting means on the property and place one at each location.
Provide a 10' vegetation free area around the array.
Recall inspection when completed.
|
|
10/12/2020 | PGE ELECTRIC TAG | ADAM KINGSLEY | PASS | eTRAKiT Inspection Request | 10/9/2020 2:54:55 PM
10/9/2020 2:54 PM Michael Houar
Contact Name: Michael Houar
Site Address: 1215 BLOCK RD
Phone: 5308934741
e-Mail: TheRemodelors@att.net
10/12/2020 12:35:46 PM
akingsley changed Inspection Type from **PERMIT FINAL to PGE ELECTRIC TAG
10/12/2020 4:20:39 PM
Tag issued for 3ph 200A serving dwelling & Ag well
1. Provide supplemental ground rod or equal prior to final.
|
|
01/12/2021 | **PERMIT FINAL | RICHARD PRATT | CANCELLED | | 1/12/2021 7:09:00 AM
rpratt changed Inspection Date/Time from 01/12/2021 08:00 AM to 01/12/2021 09:30 AM
1/12/2021 8:22:31 AM
NOT READY
1/12/2021 8:28:08 AM
Cancelled with the office.
|
|
01/15/2021 | **PERMIT FINAL | ADAM KINGSLEY | PASS | eTRAKiT Inspection Request | 1/13/2021 3:20:40 PM
1/13/2021 3:20 PM Michael Houar
PM Please
Contact Name: Michael Houar
Site Address: 1215 BLOCK RD
Phone: 5308934741
e-Mail: TheRemodelors@att.net
1/15/2021 1:20:59 PM
Previous corrections are completed
|
|