11/01/2019 | PGE ELECTRIC TAG | PHILLIP MYERS | PASS | | |
|
11/19/2019 | UNDER SLAB PLUMBING | MIKE KNIGHT | PASS | AM REQUESTED | 11/19/2019 4:33:48 PM
Also approved set backs and Euler.
|
|
11/26/2019 | FOUNDATION/FOOTINGS | MIKE KNIGHT | PASS | AM REQUESTED | |
|
11/26/2019 | PRE-SLAB | MIKE KNIGHT | PASS | AM REQUESTED | |
|
01/13/2020 | ROOF NAIL | SCOTT YOUNG | PASS | AM REQUESTED | 1/13/2020 2:23:32 PM
Also looked at interior and exterior shearwall, ok to paper and dry in!
|
|
01/31/2020 | 4-WAY ROUGH FRAME | ADAM KINGSLEY | CANCELLED | | |
|
02/03/2020 | ROUGH PLUMBING | ADAM KINGSLEY | FAIL | | 2/3/2020 11:41:26 AM
Fire sprinklers permit not issued.
DWV & water supply pipes not under test.
Bathtub drain area open to subgrade. Provide mortar or concrete.
|
|
02/03/2020 | ROUGH ELECTRICAL | ADAM KINGSLEY | FAIL | | 2/3/2020 11:41:33 AM
NM cable installed in conduit under slab. Change wiring method to listed for use outside the building or equal.
|
|
02/03/2020 | EXTERIOR SIDING | ADAM KINGSLEY | PASS | 038598-01 MSG! -Msg! Scheduled by IVR. | |
|
02/10/2020 | 4-WAY ROUGH FRAME | ADAM KINGSLEY | PASS | | |
|
02/20/2020 | DRYWALL NAIL/SCREW | SCOTT YOUNG | NOT REQUIRED | AM REQUESTED | |
|
04/07/2020 | SHOWER PAN/TUB TEST | ADAM KINGSLEY | PASS | AM REQUEST JIM 510 882 7168 | 4/7/2020 6:18:14 AM
akingsley changed Inspection Date/Time from 04/07/2020 08:00 AM to 04/07/2020 4:00 PM
|
|
04/28/2020 | PGE ELECTRIC TAG | SCOTT YOUNG | PASS | | 4/28/2020 6:53:25 AM
syoung changed Inspection Date/Time from 04/28/2020 08:00 AM to 04/28/2020 2:30 PM
4/28/2020 12:26:57 PM
syoung changed Inspection Date/Time from 04/28/2020 08:00 AM to 04/28/2020 2:30 PM
4/28/2020 12:28:24 PM
syoung changed Inspection Date/Time from 04/28/2020 08:00 AM to 04/28/2020 2:30 PM
4/29/2020 6:21:59 AM
syoung changed Inspection Date/Time from 04/28/2020 08:00 AM to 04/28/2020 2:30 PM
4/29/2020 6:23:46 AM
syoung changed Inspection Date/Time from 04/28/2020 08:00 AM to 04/28/2020 2:30 PM
|
|
| ENV HEALTH RELEASE | KATTY HERNANDEZ | PASS | SEE NOTES | 10/3/2019 1:42:49 PM
HOLD FOR EHS19-0435 FINAL.
6/11/2020 10:31:42 AM
SEPTIC PERMIT RECEIVED FINAL APPROVAL.
|
|
06/12/2020 | **PERMIT FINAL | SCOTT YOUNG | FAIL | | 6/12/2020 12:56:29 PM
Anti siphon device required on all exterior hose bibs.
Alarm for fire sprinkler not working.
Fire sprinkler relief needs a 90 degree bend so as not to shower the neighbor.
Circuit for kitchen counter kicks,will not stay on.
Exterior GFCI on back of house needs to be secured.
Exterior outlet not working.
Stress crack in walk way.
6/13/2020 9:37:09 AM
Anti siphon device required on all exterior hose bibs.
Alarm for fire sprinkler not working.
Fire sprinkler relief needs a 90 degree bend so as not to shower the neighbor.
Circuit for kitchen counter kicks,will not stay on.
Exterior GFCI on back of house needs to be secured.
Exterior outlet not working.
Stress crack in walk way.
|
|
06/11/2020 | CAL FIRE FINAL INSPE | CHRIS BOYD | PASS | | 6/12/2020 6:19:24 PM
Ok to final
|
|
06/15/2020 | **PERMIT FINAL | ADAM KINGSLEY | FAIL | PM REQUESTED | 6/15/2020 2:34:17 PM
Previous corrections are completed except
SVY 6/12/2020 12:56:29 PM
Anti siphon device required on all exterior hose bibs.
|
|
02/28/1850 | NPDES | QUENTIN CARTER | | VOIDED (ALK 6/18/2020) | 6/18/2020 11:53:12 AM
Inspection voided by ALK.
|
|
06/18/2020 | **PERMIT FINAL | ADAM KINGSLEY | PASS | | 6/18/2020 11:53:56 AM
PREVIOUS CORRECTIONS COMPLETED
|
|