09/19/2019 | **PERMIT FINAL | ADAM KINGSLEY | FAIL | eTRAKiT Inspection Request | 9/18/2019 12:13:38 PM
9/18/2019 12:13 PM NOLAN LAWRENCE
Contact Name: NOLAN LAWRENCE
Site Address: 1895 GRAND AVE
Phone: 5309179956
e-Mail: OPERATIONS@phoenixsolarinc.com
9/19/2019 10:21:04 AM
1. Main electric service entrance panel buss rating exceeded & manufactures listing voided. Panel is rated 125A, new 175A disconnect/OCPD Installed (panel is listed for 125A max service disconnect) plans incorrectly specify panel as 200A. 125A * 120% = 150A MAX. 175A + 26.62A =201.62A. Replace main breaker with 125A & reduce PV back feed OR install listed equipment or equal.
2. Ground rod installed at combiner box has been cut/shortened, manufacturers listing voided & 8' earth contact not provided. Remove grounding electrode conductor & abandon cut rod or install replacement. Photo attached.
3. Identify/ label all circuits.
|