Permit No. B19-2220 Permit Type   RESIDENTIAL Site Address   14141 RACINE CIR
MAGALIA, CA 95954
Applied   07/11/2019 Applicant   KINSERS CONSTRUCTION INC
Approved   08/30/2019 Owner   SIEVERS KATHLEEN F ETAL
Issued   08/30/2019 Contractor   KINSERS CONSTRUCTION INC
Parent Permit No.   Description   REPL SFD (1280) GAR (480) COVD (85) -CAMP FIRE
  Notes  
 
  Date of Inspection Inspection Type Inspector Result Remarks Notes

NPDESQUENTIN CARTER

 08/29/2019ENV HEALTH RELEASEVANCE SEVERINPASS

 09/13/2019SERVICE PANELSCOTT YOUNGPASS033728-01 - Scheduled by IVR.

 09/19/2019FOUNDATION/FOOTINGSWOODY TOWNSENDFAIL9/19/2019 3:49:25 PM 1. Provide fix to comply with front yard 20' setbacks. Front porch foundation is 1'9" into setback. 2. Provide revision from engineer for front porch footings as built. As built isn't per approved detail.

 09/20/2019FOUNDATION/FOOTINGSWOODY TOWNSENDPASS9/20/2019 8:11:08 AM Received engineers letter to reduce depth of front porch by 2' to comply with setbacks.

 09/24/2019PRE-SLABWOODY TOWNSENDPASS9/24/2019 2:26:03 PM Install vapor barrier. 9/25/2019 9:20:28 AM Vapor barrier installed

 10/21/2019SHEARWALL/B.W.P.-EXTWOODY TOWNSENDFAIL10/21/2019 3:51:00 PM 1. Shear nail bottom plate at #4 8' living room shear and #6 32' master/bedroom 2 shear. 2. Several anchor bolts under floor need square washers. 3. Install a35/RBC shear transfer at eaves and gable ends per shear schedule in addition to h2.5 per detail sd4/7.

 10/21/2019ROOF NAILWOODY TOWNSENDFAIL10/21/2019 3:51:08 PM 1. Provide extension ladder and approved truss calcs for roof nail inspection.

 10/25/2019SHEARWALL/B.W.P.-EXTPHILLIP MYERSPASS

 10/25/2019ROOF FRAME/SHEATHINGPHILLIP MYERSPASS

 12/06/20194-WAY ROUGH FRAMEADAM KINGSLEYFAIL12/6/2019 1:30:50 PM 1. Approved energy calculations not provided for inspection. 2. Tub drain/ floor penetration exposes underfloor. Provide rat proofing (1/4" wire mesh or equal) to seal annular space around pipes. 3. Grounding terminal bar not bonded to metal sub panel enclosure. Install bonding screw or equal. 4. Roof drip edge flashing no provided, exposed roof sheathing edges. Install required flashing or equal. 5. Provide min 30" x 30" platform at service (control panel) side of attic HVAC equipment with min 24" wide unobstructed catwalk to access. Platform compromised by whole house fan, catwalk comprised by HVAC ducting.

 12/11/20194-WAY ROUGH FRAMEMIKE KNIGHTPARTIAL12/11/2019 4:16:19 PM All corrections from 12-6-19 addressed except #4, need 2" roof edge flashing per prior correction.

 02/20/2020SHOWER PAN/TUB TESTSCOTT YOUNGFAIL2/20/2020 1:07:32 PM Bladder leaked over night. Shower pan dry. Fill and call for reinspection.

 02/24/2020SHOWER PAN/TUB TESTWOODY TOWNSENDPASS

 12/06/2019UNDERFLOOR FRAMINGADAM KINGSLEYPASS

 12/06/2019UNDERFLOOR PLUMBINGADAM KINGSLEYPASS

 04/16/2020GAS TESTADAM KINGSLEYPASS4/16/2020 6:26:35 AM akingsley changed Inspection Date/Time from 04/16/2020 08:00 AM to 04/16/2020 2:00 PM 4/16/2020 2:29:32 PM Whole system

 04/16/2020**PERMIT FINALADAM KINGSLEYVOID4/16/2020 6:26:41 AM akingsley changed Inspection Date/Time from 04/16/2020 08:00 AM to 04/16/2020 2:00 PM 4/16/2020 2:29:39 PM Not ready.

 04/16/2020TAG LPGADAM KINGSLEYPASS4/16/2020 6:26:28 AM akingsley changed Inspection Date/Time from 04/16/2020 08:00 AM to 04/16/2020 2:00 PM 4/16/2020 2:29:25 PM akingsley changed Inspection Type from PGE GAS TAG to TAG LPG 4/16/2020 2:59:36 PM 250G LPG

 04/22/2020CAL FIRE FINAL INSPECHRIS BOYDPASS4/22/2020 1:16:21 PM OK to Final

 05/05/2020**PERMIT FINALADAM KINGSLEYFAIL5/5/2020 10:51:26 AM 1. Energy compliance documents not completed. Update CA energy registry to show project completed. 2. GFCI receptacle located to the right of the kitchen range tests open ground. 3. Provide min single luminaire controlled by vacancy sensor or equal in both bathrooms. 4. Provide humidistat control for environmental exhaust fans in both bathrooms. 5. Stairs from exterior deck to ground missing required handrail. Provide graspable handrail 34"-38" above stair tread nosing or equal.

 05/08/2020**PERMIT FINALWOODY TOWNSENDPASS