| ENV HEALTH RELEASE | YVETTE CASTANON | PASS | | |
|
| NPDES | | | | |
|
02/11/2019 | FOUNDATION/FOOTINGS | WOODY TOWNSEND | PASS | 026174-01 MSG! -Msg! Scheduled by IVR. | 2/11/2019 4:19:17 PM
Conduit approved.
|
|
02/27/2019 | ELECTRICAL FINAL | WOODY TOWNSEND | CANCELLED | 026577-01 - Scheduled by IVR. | 2/27/2019 2:51:00 PM
Canceled due to road closure.
|
|
04/30/2019 | **PERMIT FINAL | MIKE KNIGHT | PASS | 028251-01 - Scheduled by IVR. | 4/30/2019 3:46:25 PM
verified torque per prior inspection.
|
|
04/24/2019 | **PERMIT FINAL | SCOTT YOUNG | FAIL | 028114-01 - Scheduled by IVR. | 4/24/2019 4:07:15 PM
Plans had been resubmitted and looked at and a couple of modifications were addressed. Oneof the issues was the older Siemens box used. Plan check engineer has asked for torque verification, the contractor did not have a torque wrench and was unable to comply with the request. They will call and reschedule.
|
|
04/02/2019 | **PERMIT FINAL | SCOTT YOUNG | FAIL | PM REQUESTED | 4/3/2019 7:28:39 AM
They were asked for a UL field verification of tap. Nothing was done.
Single line diagram does not match
|
|
02/28/2019 | **PERMIT FINAL | WOODY TOWNSEND | FAIL | | 2/28/2019 1:37:20 PM
1. Provide approved plans to show line side tap, as built conductor gauge and fused disconnect at main service. Include torque specs or details on how line side tap will be done and if re listing of main service will be required. Contractor stated that approved revisions were at the County and inspector was supposed to bring them out but notes weren't given if this is true.
|
|