09/17/2019 | UNDERGROUND ELECTRIC | ADAM KINGSLEY | VOID | 033923-01 - Scheduled by IVR. | 9/17/2019 1:28:07 PM
Added to permit B18-1165 for C1D1 conduit.
|
|
09/20/2019 | FOUNDATION/FOOTINGS | MIKE KNIGHT | CANCELLED | 034076-01 - Scheduled by IVR. | |
|
09/23/2019 | UNDER SLAB PLUMBING | ADAM KINGSLEY | PASS | 034077-01 - Scheduled by IVR. | 9/19/2019 4:05:46 PM
akingsley changed Inspection Type from ROUGH ELECTRICAL to UNDER SLAB PLUMBING
9/23/2019 7:51:16 AM
Cast iron DWV
9/23/2019 7:53:05 AM
Cast iron DWV
|
|
09/23/2019 | FOUNDATION/FOOTINGS | ADAM KINGSLEY | PASS | 034079-01 MSG! -Msg! Scheduled by IVR. | 9/23/2019 11:36:54 AM
Special inspection reports required for reinforcement, anchors & concrete compressive strength.
|
|
09/26/2019 | PRE-SLAB | WOODY TOWNSEND | PASS | 034288-01 MSG! -Msg! Scheduled by IVR. | |
|
10/15/2019 | PRE-SLAB | ADAM KINGSLEY | PARTIAL | 035076-01 - Scheduled by IVR. | 10/15/2019 3:24:00 PM
akingsley changed Inspection Type from PIER/COLUMN FOOTINGS to PRE-SLAB
10/15/2019 4:04:44 PM
akingsley changed Inspection Type from PIER/COLUMN FOOTINGS to PRE-SLAB
10/15/2019 4:11:35 PM
Trash enclosure slab & footings.
|
|
10/31/2019 | ROUGH PLUMBING | ADAM KINGSLEY | PASS | | |
|
10/31/2019 | ROUGH MECHANICAL | ADAM KINGSLEY | PARTIAL | | 10/31/2019 5:11:22 PM
Rooftop HVAC condensate pipes only
11/4/2019 3:50:41 PM
Rooftop HVAC condensate pipes only
|
|
10/31/2019 | ROUGH ELECTRICAL | ADAM KINGSLEY | PARTIAL | | 11/4/2019 3:50:46 PM
Conduit, boxes, BC only, ok to cover cooler area only.
|
|
11/25/2019 | STUCCO (LATH) | SCOTT YOUNG | PASS | 036394-01 MSG! -Msg! Scheduled by IVR. | |
|
12/13/2019 | ROUGH ELECTRICAL | LARRY AKERS | PARTIAL | 037075-01 - Scheduled by IVR. | 12/13/2019 1:20:01 PM
All can lights inspected.
|
|
02/04/2020 | SERVICE PANEL | ADAM KINGSLEY | PASS | 038674-01 - Scheduled by IVR. | 2/4/2020 3:31:14 PM
akingsley changed Inspection Type from ROUGH ELECTRICAL to SERVICE PANEL
2/4/2020 3:45:50 PM
Service switchgear & interior sub switchgear included.
Equipment listed 65k AIC
Electric tag issued
|
|
02/13/2020 | T-BAR CEILING | ADAM KINGSLEY | FAIL | 038978-02 - Scheduled by IVR. | 2/13/2020 12:26:03 PM
Lights & fixture seismic attachments not installed.
|
|
02/13/2020 | PGE GAS TAG | ADAM KINGSLEY | PASS | 038978-01 - Scheduled by IVR. | 2/13/2020 12:26:09 PM
akingsley changed Inspection Type from GAS PIPING to PGE GAS TAG
|
|
10/29/2019 | SHEARWALL/B.W.P.-EXT | ADAM KINGSLEY | PASS | 035507-01 - Scheduled by IVR. | 10/29/2019 2:01:46 PM
Unable to add inspection in the field.
Shearwall exterior & interior- pass
Roof nail -Fail
1. Missing MSI26 straps at double truss/RED I joist connections per detail 8/S2.5. Provide engineer of record written approval or fix or equal.
|
|
02/18/2020 | ROUGH FRAME | ADAM KINGSLEY | PASS | | 2/18/2020 12:07:48 PM
akingsley changed Inspection Type from ROUGH MECHANICAL to ROUGH FRAME
|
|
02/18/2020 | ROUGH ELECTRICAL | ADAM KINGSLEY | PARTIAL | | 2/19/2020 8:33:31 AM
The following elements/items have not been installed at present:
Leak system/vapor recovery control & alarm panel
Ceiling light fixtures w/seismic strap (T-bar ceiling)
Circuit conductors to Class I Div I locations & conduit seals
|
|
03/05/2020 | ROUGH ELECTRICAL | ADAM KINGSLEY | PARTIAL | 039753-01 - Scheduled by IVR. | 3/5/2020 11:57:01 AM
The following items remain
ALK 2/19/2020 8:33:31 AM
1. The following elements/items have not been installed at present:
2. Leak system/vapor recovery control & alarm
3. COMPLETE
4. Circuit conductors to Class I Div I locations & conduit seals
|
|
03/05/2020 | T-BAR CEILING | ADAM KINGSLEY | PASS | | 3/5/2020 11:57:08 AM
Provide special inspection (per plans) report prior to final
|
|
03/10/2020 | FIRE MARSHAL CLEARAN | CHRIS BOYD | PASS | | 3/11/2020 3:31:18 PM
Ok to final
|
|
03/12/2020 | ROUGH ELECTRICAL | ADAM KINGSLEY | PASS | 039951-01 - Scheduled by IVR. | |
|
03/12/2020 | ELECTRICAL FINAL | ADAM KINGSLEY | PARTIAL | | 3/12/2020 12:12:35 PM
1. Unable to verify AIC label, equipment locked. Provide access to verify maximum available fault current/ AIC rating label at main electric service entrance.
|
|
03/13/2020 | PLUMBING FINAL | ADAM KINGSLEY | PASS | 040005-01 - Scheduled by IVR. | 3/13/2020 11:14:54 AM
1. Paint/protect exposed ABS vent terminations on roof prior to permit final.
|
|
03/13/2020 | ROUGH MECHANICAL | ADAM KINGSLEY | PASS | | |
|
03/13/2020 | ELECTRICAL FINAL | ADAM KINGSLEY | PASS | | |
|
03/16/2020 | **PERMIT FINAL | ADAM KINGSLEY | FAIL | 040079-01 - Scheduled by IVR. | 3/17/2020 7:48:22 AM
1. Missing parking space & tow information accessibility signage outside the building.
2. Toilet paper dispenser not located within 7"-9" front of the water closet served at bathroom adjacent to north wall.
3. City of Gridley final approval required
4. Butte County Environmental Health (PH Food Service) Final approval required.
|
|
03/17/2020 | CITY OF GRIDELY FINAL | CITY OF GRIDLEY | PASS | | |
|
03/17/2020 | ENV HEALTH RELEASE | YVETTE CASTANON | PASS | | 3/19/2020 1:47:35 PM
ENV HEALTH RELEASE
This gas station mini mart has been reviewed, inspected and permitted by the Environmental Health Division as a Food Facility and as an Underground Storage Tank CUPA permitted facility. Environmental Health approves the occupancy and use of this facility for its intended purpose.
- Doug
Doug Danz
Butte County Public Health
|
|
03/19/2020 | **PERMIT FINAL | CURTIS L. JOHNSON | PARTIAL | 040135-02 - Scheduled by IVR. | 3/19/2020 1:49:59 PM
Other Departments have approve, 30-Day TCO provided. Call back for inspection of remaining building corrections.
|
|
06/17/2020 | **PERMIT FINAL | ADAM KINGSLEY | PASS | 042908-03 - Scheduled by IVR. | 6/17/2020 1:40:56 PM
Previous corrections are completed
|
|