02/12/2019 | **PERMIT FINAL | SCOTT YOUNG | FAIL | eTRAKiT Inspection Request | 2/8/2019 11:44:42 AM
2/8/2019 11:45 AM C E S ELECTRIC
Can we please get a courtesy call 30min to inspection ( Dan @ 774.7429) Thank you
Contact Name: C E S ELECTRIC
Site Address: 5370 CHURCH ST
Phone: 5306364257
e-Mail: CESJEREMY@GMAIL.COM
2/12/2019 8:49:54 AM
Torque report or visually watch contractor torque to manufacturer's specs
|
|
08/30/2018 | **PERMIT FINAL | ADAM KINGSLEY | FAIL | 021919-01 - Scheduled by IVR. | 8/30/2018 1:28:44 PM
1. Equipment has not been field torqued. Provide completed torque report for required connections in the listed switchgear/ SE cabinets.
2. Bank of PV arrays and inverter omitted. Provide revised electric line diagram and layout.
|
|
02/15/2019 | **PERMIT FINAL | ADAM KINGSLEY | PASS | | |
|
02/28/1850 | ENV HEALTH RELEASE | DARREN JONES | | VOIDED (ADAM KINGSLEY 2/15/2019) | |
|
02/28/1850 | NPDES | | | VOIDED (ADAM KINGSLEY 2/15/2019) | |
|