05/15/2025
4:55 PM

Butte County
Department of Development Services

Main: 530.552.3700
Automated Inspection Phone Line: 530.538.4365
Online Inspection Scheduling / Payments / Renewals:
ButteCounty.net/DDS

 
Permit No. B24-2538 Permit Type   SOLAR ONLINE Site Address   2244 LONE TREE RD
OROVILLE, CA 95965
Applied   10/07/2024 Applicant   RCI SOLAR INC
Approved   04/29/2025 Owner   GRAVES MITCHEL E & KALEA C
Issued   04/30/2025 Contractor   RCI SOLAR INC
Parent Permit No.   Description   GRND MNT SOLAR 14.8KW (REPLACES B23-1388)
  Notes   This project was initially installed by another contractor and they failed to call for trench and footing inspections for the piers. They uninstalled everything but the underground electrical. We will be re-installing the equipment and digging new piers.
 
  Date of Inspection Inspection Type Inspector Result Remarks Notes

 05/06/2025PIER/COLUMN FOOTINGSWOODY TOWNSENDPASS078319-01 - Scheduled by IVR.5/6/2025 3:49:02 PM Setbacks and footings approved

 05/12/2025UNDERGROUND ELECTRICRANDALL SMITHFAIL078414-01 - Scheduled by IVR.5/12/2025 5:01:22 PM 1. Provide sand or clean fill for a minimum of 12 inches over the conduit or equal. CEC 300.5(F) 2. Call for reinspection when corrections are completed.

 05/13/2025UNDERGROUND CONDUITWOODY TOWNSENDPASS5/13/2025 8:34:10 AM Approved sch 80 conduit to be backfilled with native soil. Back fill had minimal large angular rocks.

**PERMIT FINALSCOTT YOUNG078431-01 - Scheduled by IVR.