Permit No. B24-1016 Permit Type   MECH ELECTRIC PLUMB Site Address   42 ROSITA WAY
OROVILLE, CA 95966
Applied   04/30/2024 Applicant   ZACKER CHRISTINA & DONOVAN
Approved   04/30/2024 Owner   ZACKER CHRISTINA & DONOVAN
Issued   04/30/2024 Contractor   ZACKER CHRISTINA & DONOVAN
Parent Permit No.   Description   MPU (100A)
  Notes  
 
  Date of Inspection Inspection Type Inspector Result Remarks Notes

 05/07/2024PGE ELECTRIC TAGWOODY TOWNSENDFAIL5/6/2024 9:53:38 AM WANTS TO KNOW IF PANEL IS SAFE IN THE LOC IT IS, IF ITS FIRE HAZARD 5/7/2024 4:21:40 PM Main panel was not replaced. Complete replacement per permit description and reschedule inspection. Note for inspection has a question about a fire hazard. No hazard visible at this time. Service entrance wires on PGE side are in contact with vegetation. Contact PGE about these conductors.

 06/25/2024PGE ELECTRIC TAGRANDALL SMITHPASSCALL NOLAN 530-990-96066/25/2024 3:33:37 PM Tagged 100 a mpu

 06/25/2024**PERMIT FINALRANDALL SMITHFAIL6/25/2024 3:34:23 PM 1. Chalk/ seal service mast going through the roof eave. 2. Provide a completed smoke detector affidavit.

 07/26/2024**PERMIT FINALRANDALL SMITHFAIL7/26/2024 2:12:08 PM None of the previous corrections were completed. RJS 6/25/2024 3:34:23 PM 1. Chalk/ seal service mast going through the roof eave. 2. Provide a completed smoke detector affidavit.

 08/01/2024**PERMIT FINALRANDALL SMITHPASS8/1/2024 4:24:02 PM All previous corrections were completed