Permit No. B24-0852 Permit Type   SOLAR ONLINE Site Address   131 PALERMO DR
OROVILLE, CA 95966
Applied   04/15/2024 Applicant   BRIGHT PLANET SOLAR INC
Approved   04/16/2024 Owner   CLINGMAN ERIC J & JEANICE M
Issued   04/17/2024 Contractor   BRIGHT PLANET SOLAR INC
Parent Permit No.   Description   10.8 KW ROOF MOUNT SOLAR ON RES, 2 BATT
  Notes  
 
  Date of Inspection Inspection Type Inspector Result Remarks Notes

 06/06/2024**PERMIT FINALRANDALL SMITHFAILeTRAKiT Inspection Request5/30/2024 12:16:47 PM 5/30/2024 12:16 PM BRIGHT PLANET SOLAR INC Contact Name: Bodhi Site Address: 131 PALERMO DR Phone: 7072355927 e-Mail: bodhid@brightops.com 6/6/2024 4:21:27 PM 1. Provide a 40 amp PV breaker to comply with the 120% rule or provide a system summary report showing the property owners name, address and the output current limit . (32a on plans) 2. Provide a completed smoke detector affidavit.

 07/26/2024**PERMIT FINALRANDALL SMITHPASSeTRAKiT Inspection Request7/17/2024 12:41:54 PM 7/17/2024 12:41 PM BRIGHT PLANET SOLAR INC Contact Name: Bodhi Site Address: 131 PALERMO DR Phone: 7072355927 e-Mail: bodhid@brightops.com 7/17/2024 1:30:16 PM 7/17/2024 1:30 PM BRIGHT PLANET SOLAR INC Contact Name: Bodhi Site Address: 131 PALERMO DR Phone: 7072355927 e-Mail: bodhid@brightops.com 7/26/2024 2:11:59 PM All previous corrections were completed