07/17/2024 | **PERMIT FINAL | WOODY TOWNSEND | FAIL | eTRAKiT Inspection Request | 7/12/2024 1:42:59 PM
7/12/2024 1:42 PM BRIGHT PLANET SOLAR INC
Contact Name: Bodhi
Site Address: 9445 CORBETT CT
Phone: 7072355927
e-Mail: bodhid@brightops.com
7/17/2024 4:49:13 PM
Locate existing or install new grounding electrodes.
|
|
07/26/2024 | **PERMIT FINAL | CHRISTOPHER ROBERTS | FAIL | eTRAKiT Inspection Request | 7/19/2024 9:45:11 AM
7/19/2024 9:45 AM BRIGHT PLANET SOLAR INC
Contact Name: Bodhi
Site Address: 9445 CORBETT CT
Phone: 7072355927
e-Mail: bodhid@brightops.com
7/26/2024 7:07:38 AM
rpratt changed Inspection Date/Time from 07/26/2024 08:00 AM to 07/26/2024 09:30 AM
7/26/2024 7:10:14 AM
rpratt changed Inspection Date/Time from 07/26/2024 09:30 AM to 07/26/2024 10:30 AM
7/26/2024 8:40:43 AM
croberts changed Inspection Date/Time from 07/26/2024 10:30 AM to 07/26/2024 12:00 PM
7/26/2024 8:45:54 AM
croberts changed Inspection Date/Time from 07/26/2024 12:00 PM to 07/26/2024 11:30 AM
7/26/2024 9:22:17 AM
croberts changed Inspection Date/Time from 07/26/2024 11:30 AM to 07/26/2024 11:00 AM
7/26/2024 11:01:26 AM
1. Ground rods that were installed per prior correction are required to be at LEAST 6' apart. Ground rods are currently 5' apart (see pic)
Move or drive new ground rod 6'+ from primary ground rod.
Complete work and call for re-inspection
|
|
08/14/2024 | **PERMIT FINAL | WOODY TOWNSEND | PASS | AM if possible | 8/9/2024 9:19:56 AM
8/9/2024 9:19 AM BRIGHT PLANET SOLAR INC
AM if possible
Contact Name: Bodhi
Site Address: 9445 CORBETT CT
Phone: 7072355927
e-Mail: bodhid@brightops.com
|
|