03/14/2024 | FOUNDATION/FOOTINGS | RANDALL SMITH | FAIL | across from Longview Ct | 3/14/2024 3:35:40 PM
1. Provide an updated site plan to Butte County Permit Center showing actual setback of 32 ft from the front for approval.
2. Complete installation of rebar in the footings and slab.
3. Call for reinspection when corrections are completed.
|
|
03/18/2024 | FOUNDATION/FOOTINGS | RANDALL SMITH | PASS | AM PLEASE - CONCRETE POUR AT 10 | 3/18/2024 3:16:48 PM
Ok to pour
|
|
03/18/2024 | SETBACKS | RANDALL SMITH | PASS | | 3/18/2024 3:16:56 PM
Setbacks met approved revised plan.
|
|
05/01/2024 | PGE ELECTRIC TAG | RANDALL SMITH | FAIL | AM PLEASE | 5/1/2024 4:18:14 PM
Main panel was not installed yet. Advised owner to install main panel then call for green tag.
Before final can be completed,
1. Provide 2% slope for 10 ft from building or equal on south and west sides.
2. Provide a 36 inch by width of door landing at man door.
3. Complete electrical installation.
|
|
05/23/2024 | TAG ELECTRIC | CHRISTOPHER ROBERTS | PASS | eTRAKiT Inspection Request | 5/21/2024 3:01:03 PM
5/21/2024 3:01 PM W ELECTRIC ENTERPRISES INC
Contact Name: W ELECTRIC ENTERPRISES INC
Site Address: AVACADO RD
Phone: 5307173253
e-Mail: wee.incorporated@gmail.com
5/23/2024 3:31:01 PM
PGE electric tag - Approved
|
|
05/23/2024 | **PERMIT FINAL | CHRISTOPHER ROBERTS | FAIL | | 5/23/2024 3:31:21 PM
1. Landing at man door for shop is 8" lower than threshold of door, exterior man door swings out over landing. Landings must be at least 1.5" from door threshold per code R311.3.1
** Electrical, and shop inspected.
|
|
03/14/2025 | CAL FIRE FINAL INSPE | CHRIS BOYD | PASS | | 3/14/2025 10:58:50 AM
Ok to final
|
|