| CAL FIRE FINAL INSPE | CHRIS BOYD | | | |
|
04/26/2024 | ENV HEALTH RELEASE | ALANA KONG | | SEE NOTES | 4/26/2024 11:13:45 AM
Pending septic final EHS23-0298
|
|
| CONSTRUCTION POWER | DSINSPECTION | | VOIDED (RDP 5/20/2024) | 5/15/2024 6:07:27 PM
5/15/2024 6:07 PM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
5/16/2024 7:03:42 PM
5/16/2024 7:03 PM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
5/20/2024 6:47:29 PM
Inspection voided by RDP. Most recent remarks follow: Rebar Inspection
|
|
| FOUNDATION/FOOTINGS | DSINSPECTION | | eTRAKiT Inspection Request | 5/21/2024 3:48:53 PM
5/21/2024 3:48 PM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
|
|
| FOUNDATION/FOOTINGS | DSINSPECTION | | AM inspection if possible please. | 5/21/2024 4:07:44 PM
5/21/2024 4:07 PM Josh Grigg
AM inspection if possible please.
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
|
|
| FORMS/STEEL/HOLDOWNS | DSINSPECTION | | AM inspection if possible. | 5/21/2024 4:10:10 PM
5/21/2024 4:10 PM Josh Grigg
AM inspection if possible please.
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
|
|
05/22/2024 | UFER GROUND | SCOTT YOUNG | PASS | eTRAKiT Inspection Request | 5/16/2024 10:37:53 PM
5/16/2024 10:37 PM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
5/22/2024 6:08:29 AM
Upher -approved
5/22/2024 6:12:23 AM
Upher -approved
5/22/2024 6:13:38 AM
Upher -approved
|
|
05/22/2024 | UNDERGROUND PLUMBING | SCOTT YOUNG | FAIL | eTRAKiT Inspection Request | 5/16/2024 7:22:02 PM
5/16/2024 7:22 PM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
5/22/2024 6:08:35 AM
Plans not onsite,unable to complete inspection
5/22/2024 6:12:30 AM
Plans not onsite,unable to complete inspection
5/22/2024 6:13:45 AM
Plans not onsite,unable to complete inspection
|
|
05/22/2024 | FOUNDATION/FOOTINGS | SCOTT YOUNG | FAIL W/RE-INSP FEE | eTRAKiT Inspection Request | 5/16/2024 7:22:01 PM
5/16/2024 7:22 PM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
5/22/2024 6:08:42 AM
Contractor did not show up today with plans.
Reinspection fee added .
Please pay inspection fee prior to next inspection.
5/22/2024 6:12:37 AM
Contractor did not show up today with plans.
Reinspection fee added .
Please pay inspection fee prior to next inspection.
5/22/2024 6:13:51 AM
Contractor did not show up today with plans.
Reinspection fee added .
Please pay inspection fee prior to next inspection.
|
|
05/22/2024 | FORMS/STEEL/HOLDOWNS | SCOTT YOUNG | FAIL | eTRAKiT Inspection Request | 5/16/2024 7:22:02 PM
5/16/2024 7:22 PM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
5/22/2024 6:08:49 AM
Approved plans required onsite
5/22/2024 6:12:43 AM
Approved plans required onsite
5/22/2024 6:13:58 AM
Approved plans required onsite
|
|
05/21/2024 | CONSTRUCTION POWER | SCOTT YOUNG | PASS | Meter Release | 5/15/2024 6:09:32 PM
5/15/2024 6:09 PM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
5/22/2024 6:08:56 AM
Meter release issued
5/22/2024 6:12:50 AM
Meter release issued
5/22/2024 6:14:05 AM
Meter release issued
|
|
05/23/2024 | FOUNDATION/FOOTINGS | SCOTT YOUNG | PASS | AM inspection if possible please. | 5/21/2024 4:11:37 PM
5/21/2024 4:11 PM Josh Grigg
AM inspection if possible please.
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
5/24/2024 6:16:39 AM
Approved
See attachments for pictures.
|
|
05/24/2024 | FORMS/STEEL/HOLDOWNS | SCOTT YOUNG | PASS | eTRAKiT Inspection Request | 5/21/2024 3:48:52 PM
5/21/2024 3:48 PM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
5/24/2024 6:16:46 AM
Approved
5/24/2024 6:20:03 AM
Hold downs and hardware approved
|
|
06/13/2024 | UNDERFLOOR FRAMING | SCOTT YOUNG | PASS | eTRAKiT Inspection Request | 6/10/2024 7:08:42 AM
6/10/2024 7:08 AM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
6/17/2024 5:54:43 AM
Underfloor framing- Approved
|
|
06/13/2024 | UNDERFLOOR PLUMBING | SCOTT YOUNG | FAIL | eTRAKiT Inspection Request | 6/10/2024 7:03:36 AM
6/10/2024 7:03 AM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
6/17/2024 5:54:51 AM
Plumbing - Fail
See attachments for pictures of cracked waste line.
Pipe will need to be replaced.
This can be looked at at next inspection.
There is an access crawl approximately 10' from split pipe.
|
|
09/03/2024 | UNDERFLOOR PLUMBING | WOODY TOWNSEND | CANCELLED | eTRAKiT Inspection Request | 8/28/2024 5:48:16 PM
8/28/2024 5:48 PM Josh Grigg
Partial at Cathedral Ceiling
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
|
|
09/03/2024 | ROOF FRAME/SHEATHING | WOODY TOWNSEND | PARTIAL | eTRAKiT Inspection Request | 8/28/2024 5:48:16 PM
8/28/2024 5:48 PM Josh Grigg
Partial at Cathedral Ceiling
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
9/3/2024 5:03:48 PM
wtownsend changed Inspection Type from PROGRESS INSPECTION to ROOF FRAME/SHEATHING
9/3/2024 5:12:16 PM
Framing, electrical Fire sprinklers at t&g ceiling.
|
|
| FIRE SPRINKLERS | DSINSPECTION | | VOIDED (RDP 9/4/2024) | 8/28/2024 5:48:16 PM
8/28/2024 5:48 PM Josh Grigg
Partial at Cathedral Ceiling
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
9/4/2024 8:48:16 PM
Inspection voided by RDP. Most recent remarks follow: eTRAKiT Inspection Request
|
|
09/04/2024 | TRUSS ROOF | RICHARD PRATT | CANCELLED | eTRAKiT Inspection Request | 8/28/2024 5:52:34 PM
8/28/2024 5:52 PM Josh Grigg
Partial at Cathedral Ceiling
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
9/4/2024 3:51:29 PM
From: Josh Grigg
Sent: Wednesday, September 4, 2024 3:16 PM
To: DSBuilding
Cc: Townsend, Woody
Subject: Cancel Inspections for B23-2305
. ATTENTION: This message originated from outside Butte County. Please exercise judgment before opening attachments, clicking on links, or replying. .
Hi,
Sorry I just missed the window to cancel inspections tomorrow for our project in Butte Meadows.
For B23-2305 can you cancel the inspections for tomorrow (9/5/24) it was Truss Roof and Rough Electrical.
I believe I canceled fire sprinkler in time.
Thanks
Josh Grigg
GMH Builders, Inc.
O:707-757-5050
C: 707.718.2233
Josh@gmhbuild.com
P: 19150 Sonoma Highway, Sonoma CA 95476
M: PO 1773, Sonoma, CA 95476
|
|
09/04/2024 | ROUGH ELECTRICAL | RICHARD PRATT | CANCELLED | eTRAKiT Inspection Request | 8/28/2024 5:52:34 PM
8/28/2024 5:52 PM Josh Grigg
Partial at Cathedral Ceiling
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
9/4/2024 3:51:21 PM
From: Josh Grigg
Sent: Wednesday, September 4, 2024 3:16 PM
To: DSBuilding
Cc: Townsend, Woody
Subject: Cancel Inspections for B23-2305
. ATTENTION: This message originated from outside Butte County. Please exercise judgment before opening attachments, clicking on links, or replying. .
Hi,
Sorry I just missed the window to cancel inspections tomorrow for our project in Butte Meadows.
For B23-2305 can you cancel the inspections for tomorrow (9/5/24) it was Truss Roof and Rough Electrical.
I believe I canceled fire sprinkler in time.
Thanks
Josh Grigg
GMH Builders, Inc.
O:707-757-5050
C: 707.718.2233
Josh@gmhbuild.com
P: 19150 Sonoma Highway, Sonoma CA 95476
M: PO 1773, Sonoma, CA 95476
|
|
09/12/2024 | ROOF NAIL | SCOTT YOUNG | FAIL | eTRAKiT Inspection Request | 9/10/2024 10:05:31 AM
9/10/2024 10:05 AM Josh Grigg
Sheathing at Conditioned Area
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
9/13/2024 6:11:24 AM
Roof not completed, framing not completed.
Half of sheathing down only.
See Attachments for pictures
Contractor trying to get insulation sprayed in, roof framing completed and sheathing down by Friday afternoon to beat the rain.
|
|
09/12/2024 | ROOF FRAME/SHEATHING | SCOTT YOUNG | FAIL | eTRAKiT Inspection Request | 9/10/2024 10:05:30 AM
9/10/2024 10:05 AM Josh Grigg
Sheathing at Conditioned Area
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
9/13/2024 6:11:32 AM
Roof framing not complete
See attachment for pictures
|
|
| ROOF FRAME/SHEATHING | DSINSPECTION | | eTRAKiT Inspection Request | 9/20/2024 7:58:55 AM
9/20/2024 7:58 AM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
|
|
| UNDERGROUND PLUMBING | DSINSPECTION | | eTRAKiT Inspection Request | 9/23/2024 9:26:46 PM
9/23/2024 9:26 PM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
|
|
| UNDERGROUND PROPANE | DSINSPECTION | | eTRAKiT Inspection Request | 9/23/2024 9:26:46 PM
9/23/2024 9:26 PM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
|
|
| UNDERGROUND ELECTRIC | DSINSPECTION | | eTRAKiT Inspection Request | 9/23/2024 9:26:47 PM
9/23/2024 9:26 PM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
|
|
| UNDERGROUND ELECTRIC | DSINSPECTION | | eTRAKiT Inspection Request | 10/1/2024 5:25:17 PM
10/1/2024 5:25 PM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
|
|
| UNDERGROUND PLUMBING | DSINSPECTION | | eTRAKiT Inspection Request | 10/1/2024 5:25:18 PM
10/1/2024 5:25 PM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
|
|
09/26/2024 | ROOF NAIL | CHRISTOPHER ROBERTS | PASS | eTRAKiT Inspection Request | 9/20/2024 7:58:56 AM
9/20/2024 7:58 AM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
9/23/2024 9:27:48 PM
9/23/2024 9:27 PM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
9/26/2024 2:51:50 PM
Roof nail - Approved
Okay to cover
|
|
| UNDERGROUND PROPANE | DSINSPECTION | | eTRAKiT Inspection Request | 10/1/2024 5:25:18 PM
10/1/2024 5:25 PM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
|
|
09/26/2024 | SHEARWALL/B.W.P.-EXT | CHRISTOPHER ROBERTS | PASS | | 9/26/2024 2:52:11 PM
Shearwall ext. - Approved
** cst16 straps required per plans for upstairs windows. Contractor will install straps and take pics of work so they can fully weatherproof home.
** okay to wrap.
|
|
| UNDERGROUND CONDUIT | DSINSPECTION | | eTRAKiT Inspection Request | 10/1/2024 5:25:17 PM
10/1/2024 5:25 PM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
|
|
| UNDERGROUND PROPANE | DSINSPECTION | | eTRAKiT Inspection Request | 10/9/2024 3:23:26 PM
10/9/2024 3:23 PM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
|
|
| UNDERGROUND PLUMBING | DSINSPECTION | | eTRAKiT Inspection Request | 10/9/2024 3:23:26 PM
10/9/2024 3:23 PM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
|
|
| UNDERGROUND ELECTRIC | DSINSPECTION | | eTRAKiT Inspection Request | 10/9/2024 3:23:27 PM
10/9/2024 3:23 PM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
|
|
09/26/2024 | ROOF FRAME/SHEATHING | CHRISTOPHER ROBERTS | PASS | eTRAKiT Inspection Request | 9/23/2024 9:26:47 PM
9/23/2024 9:26 PM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
9/26/2024 2:51:42 PM
Roof frame/sheathing - Approved
|
|
| UNDERGROUND CONDUIT | DSINSPECTION | | eTRAKiT Inspection Request | 10/9/2024 3:23:27 PM
10/9/2024 3:23 PM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
|
|
10/17/2024 | UNDERGROUND CONDUIT | SCOTT YOUNG | PASS | | 10/21/2024 6:18:34 AM
Inspected:
underground electric
under ground gas
septic line
water.
also inspected and approved rough plumbing , all DWV lines were full and under test.
|
|
10/21/2024 | UNDERGROUND PLUMBING | SCOTT YOUNG | PASS | | 10/22/2024 6:16:44 AM
Trench with water line -Approved
|
|
10/21/2024 | UNDERGROUND GAS | SCOTT YOUNG | PASS | | 10/22/2024 6:16:49 AM
Gas line and trench -Approved
|
|
10/21/2024 | UNDERGROUND ELECTRIC | SCOTT YOUNG | PASS | | 10/22/2024 6:16:57 AM
Underground Electrical-Approved
|
|
10/22/2024 | ROUGH PLUMBING | SCOTT YOUNG | CANCELLED | | 10/22/2024 6:36:35 AM
Cancelled, called in under house permit.
|
|
10/22/2024 | 4-WAY ROUGH FRAME | SCOTT YOUNG | PASS | eTRAKiT Inspection Request | 10/17/2024 3:57:54 PM
10/17/2024 3:57 PM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
10/23/2024 6:14:38 AM
Fire place chase not finished, interior shearwall needs to be completed after 4-way rough. Draft stop not in
Can be looked at , at shower pan inspection.
10/23/2024 6:28:36 AM
Fire place chase not finished, interior shearwall needs to be completed after 4-way rough. Draft stop not in
Can be looked at , at shower pan inspection.
|
|
02/06/2025 | DRYWALL NAIL/SCREW | CHRISTOPHER ROBERTS | VOID | eTRAKiT Inspection Request | 2/3/2025 11:01:28 AM
2/3/2025 11:01 AM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
2/6/2025 6:16:08 AM
County does not conduct drywall nail/screw inspections
|
|
04/10/2025 | SHOWER PAN/TUB TEST | CHRISTOPHER ROBERTS | PASS | eTRAKiT Inspection Request | 3/25/2025 12:18:48 PM
3/25/2025 12:18 PM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
4/1/2025 9:04:13 AM
4/1/2025 9:04 AM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
4/6/2025 10:01:01 AM
4/6/2025 10:01 AM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 5305216242
e-Mail: josh@gmhbuild.com
4/10/2025 12:54:53 PM
Shower pan/tub test - Approved
|
|
05/12/2025 | GAS TEST | RANDALL SMITH | CANCELLED | eTRAKiT Inspection Request | 5/11/2025 7:57:03 AM
5/11/2025 7:57 AM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
5/12/2025 4:46:02 PM
From: Josh Grigg
Sent: Monday, May 12, 2025 4:08 PM
To: DSBuilding
Subject: RE: B23-2305 Cancel Inspection
. ATTENTION: This message originated from outside Butte County. Please exercise judgment before opening attachments, clicking on links, or replying. .
Hi,
With the late snow we got today and possibly more tomorrow, we wont be ready for the gas test inspection tomorrow. Can you please cancel it.
Permit Number
B23-2305
Thanks
Josh Grigg
GMH Builders, Inc.
O:707-757-5050
C: 707.718.2233
|
|
| GAS TEST | CHRISTOPHER ROBERTS | | eTRAKiT Inspection Request | 4/21/2025 2:16:40 PM
4/21/2025 2:16 PM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
5/12/2025 4:15:09 PM
5/12/2025 4:15 PM Josh Grigg
Contact Name: Josh Grigg
Site Address: 7364 MEADOW CREEK DR
Phone: 7077182233
e-Mail: josh@gmhbuild.com
|
|