12/15/2023 | FOUNDATION/FOOTINGS | RICHARD PRATT | PASS | eTRAKiT Inspection Request | 12/13/2023 6:43:52 AM
12/13/2023 6:43 AM Justin O’Rear
Contact Name: Justin O’Rear
Site Address: 2920 ALAMO AVE
Phone: 5305189173
e-Mail: Jorconstruction@gmail.com
12/15/2023 6:12:29 AM
rpratt changed Inspection Date/Time from 12/15/2023 08:00 AM to 12/15/2023 10:00 AM
12/15/2023 12:35:27 PM
Forms, footings and rebar - Approved
|
|
12/15/2023 | SETBACKS | RICHARD PRATT | PASS | | 12/15/2023 12:35:35 PM
Setbacks- Checked and Approved
|
|
12/15/2023 | PIER/COLUMN FOOTINGS | RICHARD PRATT | PASS | | 12/15/2023 12:35:45 PM
Pier footings- checked and Approved
|
|
12/15/2023 | FORMS/STEEL/HOLDOWNS | RICHARD PRATT | PASS | | 12/15/2023 12:35:53 PM
Forms, steel and hold downs - Approved
|
|
01/02/2024 | UNDERFLOOR FRAMING | CHRISTOPHER ROBERTS | PASS | eTRAKiT Inspection Request | 12/27/2023 6:58:34 PM
12/27/2023 6:58 PM Justin O’Rear
Contact Name: Justin O’Rear
Site Address: 2920 ALAMO AVE
Phone: 5305189173
e-Mail: Jorconstruction@gmail.com
1/2/2024 9:14:22 AM
Underfloor framing - Approved
|
|
01/02/2024 | UNDERFLOOR PLUMBING | CHRISTOPHER ROBERTS | PASS | | 1/2/2024 9:14:28 AM
Underfloor plumbing - Approved
|
|
01/31/2024 | ROOF FRAME/SHEATHING | RANDALL SMITH | PASS | eTRAKiT Inspection Request | 1/29/2024 3:42:52 PM
1/29/2024 3:42 PM Justin O’Rear
Contact Name: Justin O’Rear
Site Address: 2920 ALAMO AVE
Phone: 5305189173
e-Mail: Jorconstruction@gmail.com
1/31/2024 4:10:22 PM
Ok to dry in
|
|
01/31/2024 | SHEARWALL/B.W.P.-EXT | RANDALL SMITH | PASS | | 1/31/2024 4:10:51 PM
Ok to dry in
|
|
03/11/2024 | STUCCO (LATH) | WOODY TOWNSEND | PASS | eTRAKiT Inspection Request | 3/7/2024 4:01:05 PM
3/7/2024 4:01 PM Justin O’Rear
Contact Name: Justin O’Rear
Site Address: 2920 ALAMO AVE
Phone: 5305189173
e-Mail: Jorconstruction@gmail.com
|
|
03/11/2024 | 4-WAY ROUGH FRAME | WOODY TOWNSEND | FAIL | eTRAKiT Inspection Request | 3/7/2024 4:01:04 PM
3/7/2024 4:01 PM Justin O’Rear
Contact Name: Justin O’Rear
Site Address: 2920 ALAMO AVE
Phone: 5305189173
e-Mail: Jorconstruction@gmail.com
3/11/2024 4:34:35 PM
1. Bond metal elec. boxes.
2. Rat proof tubs/seal around pipes.
3. Bond gas pipe.
4. Install nail protection at master bath vent/ top plate.
7. Complete electrical at attic FAU.
8. Provide approved fire sprinkler plans. Currently holding test.
|
|
03/14/2024 | TAG ELECTRIC | RICHARD PRATT | CANCELLED | eTRAKiT Inspection Request | 3/12/2024 3:26:59 PM
3/12/2024 3:26 PM Justin O’Rear
Contact Name: Justin O’Rear
Site Address: 2920 ALAMO AVE
Phone: 5305189173
e-Mail: Jorconstruction@gmail.com
3/14/2024 6:30:23 AM
rpratt changed Inspection Date/Time from 03/14/2024 08:00 AM to 03/14/2024 11:30 AM
3/14/2024 8:56:15 AM
CANCELLED VIA PHONE CALL
|
|
03/20/2024 | 4-WAY ROUGH FRAME | SCOTT YOUNG | PARTIAL | eTRAKiT Inspection Request | 3/18/2024 4:33:46 PM
3/18/2024 4:33 PM Justin O’Rear
Contact Name: Justin O’Rear
Site Address: 2920 ALAMO AVE
Phone: 5305189173
e-Mail: Jorconstruction@gmail.com
3/21/2024 6:25:03 AM
1. Metal pancake boxes required to be grounded with list green grounding screw.
2. Frame Attic access crawl hole. Fau placed over access on plans .
|
|
07/15/2024 | TAG ELECTRIC | CHRISTOPHER ROBERTS | PASS | | 7/15/2024 3:50:48 PM
PGE electric tag - Approved
** Main panel moved from pedestal to side of MH. Main panel is also a duel meter panel supplying power to 2924 & 2920. A permit from HCD will need to be issued and passed before Butte Co. can final project B24-0850 and B23-1587 due to meters installed on MH.
|
|
12/10/2024 | **PERMIT FINAL | WOODY TOWNSEND | FAIL | eTRAKiT Inspection Request | 12/8/2024 8:37:07 AM
12/8/2024 8:37 AM Justin O’Rear
Contact Name: Justin O’Rear
Site Address: 2920 ALAMO AVE
Phone: 5305189173
e-Mail: Jorconstruction@gmail.com
12/11/2024 9:49:42 AM
1. Install smooth kitchen hood exhaust duct.
2. Insulate exterior water pipes.
3. Replace broken attic light switch cover.
4. Provide wood stove clearances. Corner of stove to combustible is 11 3/4".( clearances approved 12/11/24)
5. Obtain PV permit, install and final permit.
6. Contact Planning, Public Works NPDES and Health Dept. for final approvals.
LPG tag and gas test approved by SY under B24-1147.
Fire sprinkler final approved.
|
|
12/10/2024 | WATER SERVICE | WOODY TOWNSEND | PASS | | 12/10/2024 3:19:22 PM
2" water main from existing shop to dwelling.
|
|
12/11/2024 | PLANNING CLEARANCE | TRISTAN WEEMS | PASS | | 5/30/2023 10:54:52 AM
If demolition permit has not been finaled, an ADU Deed Restriction will be required. Per discussion with Permit Center Supervisor DH.
|
|
04/29/2025 | NPDES | PWLANDDEV | PASS | Passed Inspection #1-NPDES-MS4 Area | 4/25/2025 5:32:31 AM
4/25/2025 5:32 AM Justin O’Rear
Contact Name: Justin O’Rear
Site Address: 2920 ALAMO AVE
Phone: 5305189173
e-Mail: Jorconstruction@gmail.com
|
|
06/18/2025 | ENV HEALTH RELEASE | DANIEL GRATTAN | PASS | SEE NOTES | 6/18/2025 1:21:08 PM
Septic finaled with AIPN recorded, as-built w/ designer sign off, and operating permit w/ service agreement. Well came back clean from bacteria and nitrates approve.
|
|
07/15/2025 | FIRE DEPT CLEARANCE | TROY HAND | PARTIAL | | 7/15/2025 12:14:53 PM
Need address sign at the driveway entrance on Alamo Ave.
|
|
| **PERMIT FINAL | DSINSPECTION | | eTRAKiT Inspection Request | 7/30/2025 7:43:52 PM
7/30/2025 7:43 PM Justin O’Rear
Contact Name: Justin O’Rear
Site Address: 2920 ALAMO AVE
Phone: 5305189173
e-Mail: Jorconstruction@gmail.com
|
|