06/23/2022 | FOUNDATION/FOOTINGS | CHRISTOPHER ROBERTS | PASS | | 6/23/2022 12:54:48 PM
Footings - approved
Ready to pour.
|
|
06/20/2023 | **PERMIT FINAL | CHRISTOPHER ROBERTS | FAIL | eTRAKiT Inspection Request | 6/15/2023 10:05:56 AM
6/15/2023 10:05 AM BUNCH ELECTRIC
Contact Name: BUNCH ELECTRIC
Site Address: 2768 NEAL RD
Phone: 5309664125
e-Mail: john@BUNCHELECTRIC.COM
6/20/2023 2:05:52 PM
No contractor or representative on-site.
NO PLANS ON FILE FOR GROUND MOUNT.
|
|
06/26/2023 | **PERMIT FINAL | RAYMOND SANDOVAL | FAIL | | 6/26/2023 11:19:21 AM
Contractor/ plans not on site.
Homeowner was unaware of inspection.
|
|
07/11/2023 | **PERMIT FINAL | CHRISTOPHER ROBERTS | FAIL | eTRAKiT Inspection Request | 7/10/2023 8:21:11 AM
7/10/2023 8:21 AM BUNCH ELECTRIC
Plans are folded up by AC disconnect and main panel****
Contact Name: BUNCH ELECTRIC
Site Address: 2768 NEAL RD
Phone: 5309664125
e-Mail: john@BUNCHELECTRIC.COM
7/11/2023 3:26:35 PM
1. Plan set does not match the work that has been done. Resubmit ground mount plans to Plan Check to reflect the work that was done.
2. Ground wire on array needs to be landed on rail with a lug.
3. Ground rod required at ground mount.
4. Clear 10' perimeter of vegetation around ground mount array.
Complete work and call for re-inspection.
|
|
09/27/2023 | **PERMIT FINAL | RANDALL SMITH | PASS | eTRAKiT Inspection Request | 9/20/2023 2:01:14 PM
9/20/2023 2:01 PM BUNCH ELECTRIC
please call 530-966-4125
Contact Name: BUNCH ELECTRIC
Site Address: 2768 NEAL RD
Phone: 5309664125
e-Mail: john@BUNCHELECTRIC.COM
9/27/2023 3:21:19 PM
Passed all previous corrections.
|
|